Price
$2,334.00
CAD
Stock
25+ In Stock
- Input Signal - Digital Communication - FOUNDATION Fieldbus Protocol
- Applicable Control Valve - Single Acting Actuator
- Connections - Electrical Connection: M20
- Optional Specifications - With Pressure Gauge
- Pressure Gauge - Scale And Calibration Unit: kgf/cm2
Specifications
Actuator Type
- Double-Acting Actuator
- Pneumatic
- Single-Acting Actuator
Air Consumption
- 0.20 scfm (0.32 Nm³/hour) at psi: 20.31 (kPa: 140, bar: 1.4) - Max.
- 0.62 scfm (1.0 Nm³/hour) at psi: 58.02 (kPa: 400, bar: 4) - Max.
Ambient Temperature Range
- -10° to 85° C (14° to 185° F) - for High Temperature Double-Acting Actuator
- -40° to 60° C (-40° to 140° F) - for Standard Double-Acting Actuator
- -40° to 85° C (-40° to 185° F) - Single-Acting Actuator
Approvals & Certifications
- CE
- CSA Explosion-proof Approval
- EMC - EN 61326-1 Class A, Table 2, EN 61326-2-5
- FM - Explosion-proof, Intrinsically Safe & Non-Incendive
- TIIS - Flameproof
BSP Connection
- 1/8” BSPT Female - Pressure Gauge Connection
Communication
- FOUNDATION Fieldbus
Current
- 1,000 A (1 x 40 µs), 100 times - for Repeating Lightning Protection
- 17 mA - Max.
- 41 mA - Max.
- Maximum
Diameter
- Outer Diameter: 0.31” to 0.47” (8 to 12 mm) for Applicable Cable - Attached Flameproof Packing Adapter
Display
- 10-Segment
Electrical Connectors
- 1/2” NPT
- G 1/2”
- G 1/2” Female - Attached Flameproof Packing Adapter
- M20
- PG13.5 Female
Enclosure Finish
- Deep Sea Moss Green (Munsell 0.6 GY3.l / 2.0 or Equivalent)
- Epoxy Resin Coating - Coating Change for Painting
- Polyurethan Resin Baked Finish
Enclosure, Body Material
- Aluminum - Die Cast
- Stainless Steel JIS SUS304 - Pressure Gauge Case
Environmental Protection
- IP65
- IP66
- NEMA 4X
Flow Capacity
- 4.1 scfm (6.6 Nm³/hour) at psi: 20.31 (kPa: 140, bar: 1.4) - Max.
- 8.5 scfm (13.7 Nm³/hour) at psi: 58.02 (kPa: 400, bar: 4) - Max.
Function
- Auto Tuning Function
- Contiuous Diagnostics
- Link Master Function
- Valve Position Detecting
Humidity
- 5 to 95 % Relative Humidity at 40° C (104° F) - Ambient Humidity Limits
Hysteresis
- 0.3 % of Span - Single-Acting Actuator
- 0.5 % of Span - Double-Acting Actuator
- 0.6 % of Span - for Single-Acting Actuator Valve Linkage
- 1 % of Span - for Double-Acting Actuator Valve Linkage
Linearity
- ± 0.5 % of Span (Including Linkages) - Single-Acting Actuator
- ± 1.0 % of Span - for Single-Acting Actuator Valve Linkage, for Double-Acting Actuator (Including Linkages)
- ± 2 % of Span - for Double-Acting Actuator Valve Linkage
Mounting
- Direct Connection for Rotary Valve
- Front of Actuator with Bracket
Mounting Position Effect
- ± 0.3 % of Span at 90° - Position Effect
NPT Connection
- 1/4” NPT Female - Air Connection
- 1/8” NPT Female - Pressure Gauge Connection
PID Configuration
- PID - One/Two PID Control Function
Power Supply
- 9-32 Vdc - Lightning Protection
Pressure Range
- psi: 0 to 150 (MPa: 0 to 1, bar: 0 to 10) for Pressure Gauge Scale - Double-Acting Cylinder
- psi: 0 to 60 (kPa: 0 to 400, bar: 0 to 4) for Pressure Gauge Scale - Diaphragm, Single-Acting Cylinder
Pressure Type
- Gauge
Ratio
- 30:1 - Equal Percentage
- 50:1 - Equal Percentage
Rotation
- ± 10° to ± 25°, 10 to 100 mm (0.4” to 4.0”) - Linear Motion
- 20° to 90° - Rotary Motion
Shock
- 10 G
Span Effect
- Within 300 % of Span - Span Adjustment Range
Supply Pressure
- psi: 20 to 60 (kPa: 140 to 400, bar: 1.4 to 4) - for Diaphragm, Single-Acting Actuator Air Supply Pressure
- psi: 30 to 100 (Kpa: 200 to 700, bar: 2 to 7) - for Double-Acting Actuator Air Supply Pressure
Supply Voltage
- 9-17.5 Vdc - for Intrinsically Safe Typical FISCO Model
- 9-24 Vdc - for Intrinsically Safe Typical Entity Model
- 9-32 Vdc - for General Use & Flameproof Typical, Conditions of Communication Line
Temperature Effect
- ± 0.08 % of Span/°C - Ambient Temperature Effect
Vibration
- 2 G, 15 to 2,000 Hz
- 4 mm at 5 to 15 Hz
Vibration Effect
- ± 2 % of Span at 2 G (15 to 2,000 Hz)
Zero Offset
- -15 to 85 % of Span - Zero Adjustment Range