RYV I/O Card Nest
Brand: Yokogawa Electric CorporationThis vertical mounting type nest is used to store relay I/O cards to fit mounting dimension of the CENTUM dedicated cabinet.
Features- Can store up to 16 units (32 channels) relay I/O cards.
- Can make mixed store of replay input and output cards in one nest.
- Can connect between nest and DCS with connector.
- Can connect with sequencer since necessary power to receive signal between nest and sequencer is supplied from the nest.
- Non-voltage contact of nest alarm terminal becomes ON when break of fuse in relay I/O cards.
Displaying prices & availability for Ohio, United States in CAD. Change location.
Models matching criteria: 3
- Power Supply - 170-264 Vac
- DCS Connection - Yokogawa Electric DCS Status Card ST2, ST3, ST4, ST5, ST6, ST7 Connection
100+ In Stock
$2,320.00
CAD
Does not ship to OH, United States
- Power Supply - 85-132 Vac
- DCS Connection - Yokogawa Electric DCS Status Card ST2, ST3, ST4, ST5, ST6, ST7 Connection
100+ In Stock
$1,040.00
CAD
Does not ship to OH, United States
- Power Supply - 24 Vdc ± 10%
- DCS Connection - Yokogawa Electric DCS Status Card ST2, ST3, ST4, ST5, ST6, ST7 Connection
50+ In Stock
$94.00
CAD
Does not ship to OH, United States
Specifications
Ambient Temperature Range
- 0° to 50° C (32° to 122° F)
Electrical Connectors
- M4 Screw Terminal
Humidity
- 5 to 90 % Relative Humidity - Normal Operating Conditions
- 5 to 95 % Relative Humidity, Non-Condensing - Operating Limit/Storage Conditions
Input
- 16-Channels
- 32-Channels
Insulation Resistance
- 100 megaohms at 500 Vdc between Relay Drive 24 Vdc Power Supply, Voltage Contact Output Power Supply, Conenctor, Alarm Terminal Ground
- 50 megaohms at 500 Vdc between Relay Drive 24 Vdc Power Supply, Voltage Contact Output Power Supply, Conenctor, Alarm Terminal Ground
Mounting
- M5 Screws
- Wall Mounted
Operating Temperature
- -10° to 60° C (14° to 140° F)
Output
- 30 Vdc, 300 mA - Alarm Output Rating
Power Supply
- For Voltage Contact Output: < 125 Vac/dc
- Load Current Capacity: 32-Channels (16 Output Cards) Total < 10 A
Storage Temperature
- -40° to 70° C (-40° to 158° F)
Supply Voltage
- 1,500 Vac/minute between Voltage Contact Power Supply, Alarm Contact Output, Connector (CN1.2.3), Power Supply, Ground - Withstand Voltage
- 170-264 Vac
- 24 Vdc ± 10 % (Ripple Content Below 10 % Peak-to-Peak)
- 500 Vac/minute between Voltage Contact Power Supply, Alarm Contact Output - Withstand Voltage
- 85-132 Vac