Approvals & Certifications
Consumption
- 156 mA at 24 Vdc - Current Consumption
- 6.6 VA at 100 Vac - Power Consumption
- 8.7 VA at 200 Vac - Power Consumption
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity
Input
- 0-70 mA DC - Input Range for Current Signal
- -300 to 300 Vdc - Input Range for Voltage Signal
- Within ± 30 Vdc - Allowable Input Level
Insulation Resistance
- 100 megaohms Min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually
Mounting
- DIN Rail Mounting
- Side by Side Multiple Mounting Base
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Power Supply Effect
- Up to ± 0.1 % of Span for a Supply Voltage Range of 85-264 Vac (47 to 63 Hz), 85-264 Vdc or 12-36 Vdc - Effects of Power Line Regulation
Resistance
- 1 Megaohm Approximately - Input Resistance for Voltage
- 100 kiloohms when Turned Off - Input Resistance for Voltage
- 100 to 1,000 ohms - Input Resistance for Current
- 2 to 250 kiloohms Min. - Allowable Load Resistance for DC Voltage Output
- 350 to 15,000 ohms, Max.
Response Time
- 50 µs for 63 % Response (10 to 90 % Change of Range)
Supply Voltage
- 1,000 Vac/minute between Output-1 & Output-2 Terminals - Withstanding Voltage
- 1,500 Vac/minute between Input (Output-1, Output-2) Terminals - Withstanding Voltage
- 10 mV-20 V - Span (DC)
- 100-240 Vac/dc (-15 %, 10 %), 50/60 Hz
- 12-36 Vdc
- 15-30 Vdc (± 20 %)
- 1-600 Vdc - Span
- 2,000 Vac/minute between Input (Output-1, Output-2), Power Supply & Grounding Terminals Mutually Except Input (Output-1, Output-2) - Withstanding Voltage
- 85-264 Vac (47 to 63 Hz)
Temperature Effect
- Up to ± 0.2 % of Span for a Temperature Change of 10° C (18° F) - Effects of Ambient Temperature Variations
Zero Offset
- 0 to 200 % - Zero Elevation (Current Signal)
- -100 to 200 % - Zero Elevation (Voltage Signal)