FQ1A/FQ1V Pulse to Analog Converter

Brand: Yokogawa Electric Corporation

The FQ1A/FQ1V is a compact, front terminal connection type pulse-to-Analog converter that receives pulse-train signals and converts them into isolated DC voltage or DC current signals.
Features
  • With built-in 12 V or 24 V power supply for pulse transmitter inputs
  • Input pulse types include current pulse, voltage pulse, non-voltage contact, and open collector contact
  • Internal filter to eliminate chattering can be specified when ordering (In cases where the input frequency range is up to 100 Hz, the pulse width is 3 Milliseconds or more)

Specifications

Accuracy

  • ± 0.3 % of Span

Consumption

  • 60 mA (FQ1V) - Current Consumption
  • 90 mA at 24 Vdc (FQ1A) - Current Consumption

Current

  • 1-24 mA DC - Span

Duty Cycle

  • 50 ± 30 % - Input Pulse Width

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Frequency

  • 0 to 10 kHz - Input Frequency
  • 10 kHz - Contact or Voltage Pulse

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Input

  • 0 to 10 kHz (Span DC: 50 Hz to 10 kHz)

Input Signal

  • -1 to 8 V -Low Level
  • 2 V or more - High Level
  • Contact Pulse
  • Current Pulse
  • Voltage Pulse

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • DIN Rail Mounting
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • -10 to 10 Vdc

Output Format

  • DC Current Output
  • DC Voltage Ouput

Power Supply

  • 12 Vdc / 30 mA - Transmitter Power Supply
  • 12 Vdc ± 10 %
  • 24 Vdc / 30 mA - Transmitter Power Supply
  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuations within the Operating Range of Power Supply Voltage Specification

Resistance

  • 1 Kiloohm - Input Resistance for Current Pulse
  • 2 to 250 kiloohms or more - Allowable Load Resistance for DC Voltage Output
  • 200 ohms - Input Resistance for Current Pulse
  • 510 ohms - Input Resistance for Current Pulse
  • 750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output

Response Time

  • 3 seconds - 500 Hz Span, Max.
  • 600 milliseconds - 500 Hz Span Min. (63 % Response (10 to 90 %))

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,500 Vac/minute between Input & (Output & Power Supply)
  • 10 mV-20 V - Span (DC)
  • 500 Vac/minute between Output & Power Supply

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Ambient Temperature Effect

Zero Offset

  • 0 to 200 % - Zero Elevation for Current Signal
  • -100 to 200 % - Zero Elevation for Voltage Signal

show more