EJX210B Wireless Pressure Transmitter

Brand: Yokogawa Electric Corporation

The high performance flange mounted differential pressure transmitter EJX210B features single crystal silicon resonant sensor and is suitable to measure levels of densities of solidifying or precipitating liquids. 

EJX210B transmits not only process variables but also the setting parameters using wireless signal. The transmitter runs on internal batteries, and the installation cost can be decreased since hard-wiring is not required. 

The communication protocol is compliant with ISA100.11a protocol specifications.
Features
  • Long Life Battery Design
    • Ultra low current consumption design using two high capacity lithium-thionyl chloride batteries provide wireless operation for years
  • Security Assured Wireless Network Joining
    • Infrared communication between the devices for wireless network configuration and parameter setting
  • Quick Update Time
    • Selectable from 0.5 second to 60 minutes for measured process value to publish wirelessly

Specifications

Accuracy

  • ± (0.025 + 0.005 URL/Span) % of Span - Reference Accuracy
  • ± (0.025 + 0.01 URL/Span) % of Span - Reference Accuracy
  • ± 0.075 % of Span - Reference Accuracy
  • ± 0.2 % of Span - 1 MPa or Higher (Absolute Pressure)

Ambient Temperature Range

  • -10° to 85° C (14° to 185° F) - Transmitter Ambient Temperature
  • -30° to 80° C (-22° to 176° F) - LCD Visible Range
  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • ATEX
  • CE ETSI EN 300328, ETSI EN 301489-1, ETSI EN 301489-17, EN 61010-1, EN 61010-2-030, EN 62311
  • CSA
  • EMC EN 61326-1 Class A, Table 2, EN 61326-2-3
  • FCC Approval
  • FM
  • IC
  • IEC 61518
  • IECEx
  • PED 2014/68/EU (From 19th July, 2016)
  • PED 97/23/EC (Until 18th July, 2016)

Battery Life

  • 10-Years at 60 seconds
  • 4-Years at 10 seconds

BSP Connection

  • 1/2” BSPT Female
  • 1/4” BSPT Female

Communication

  • Data Rate: 250 Kbps
  • ISA 100.11a
  • Wireless

Dead Time

  • 100 milliseconds (Nominal)

Diagnostics

  • Amplifier Failure - Self Diagnostics
  • Battery, Wireless Communication Alarm - Self Diagnostics
  • Capsule Failure - Self Diagnostics
  • Configuration Error - Self Diagnostics
  • Over-Range Error - Self Diagnostics

Diaphragm Material

  • 316L Stainless Steel
  • Hastelloy C-276 - Capsule
  • Tantalum

Display

  • 5-Digit Numerical Display - Integral Indicator
  • 6-Digit Unit Display - Integral Indicator
  • Bar Graph - Integral Indicator
  • LCD Display

Drain, Vent Valves & Plug

  • 316 Stainless Steel

Enclosure Finish

  • Mint Green Paint (Munsell 5.6 BG 3.3/2.9 or its Equivalent)

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Fill Material

  • Fluorinated Oil - Fill Fluid
  • Silicone Oil - Fill Fluid

Flange Material

  • 304 Stainless Steel
  • 316 Stainless Steel - Name Plate & Tag
  • 316L Stainless Steel - Cover
  • ASTM CF-8M - Cover, Process Connector
  • JIS S25C

Flange Size - 1-1/2” (DN 40)

  • 1-1/2” (DN 40) - 150# ANSI/JPI
  • 1-1/2” (DN 40) - 300# ANSI/JPI
  • 1-1/2” (DN 40) - JIS 10K
  • 1-1/2” (DN 40) - JIS 20K
  • 1-1/2” (DN 40) - PN 10
  • 1-1/2” (DN 40) - PN 16
  • 1-1/2” (DN 40) - PN 25
  • 1-1/2” (DN 40) - PN 40

Flange Size - 2” (DN 50)

  • 2” (DN 50) - 150# ANSI/JPI
  • 2” (DN 50) - 300# ANSI/JPI
  • 2” (DN 50) - JIS 10K
  • 2” (DN 50) - JIS 20K
  • 2” (DN 50) - PN 10
  • 2” (DN 50) - PN 16
  • 2” (DN 50) - PN 25
  • 2” (DN 50) - PN 40

Flange Size - 3” (DN 80)

  • 3” (DN 80) - 150# ANSI/JPI
  • 3” (DN 80) - 300# ANSI/JPI
  • 3” (DN 80) - JIS 10K
  • 3” (DN 80) - JIS 20K
  • 3” (DN 80) - PN 10
  • 3” (DN 80) - PN 16
  • 3” (DN 80) - PN 25
  • 3” (DN 80) - PN 40

Flange Size - 4” (DN 100)

  • 4” (DN 100) - 150# ANSI/JPI
  • 4” (DN 100) - 300# ANSI/JPI
  • 4” (DN 100) - JIS 10K
  • 4” (DN 100) - JIS 20K
  • 4” (DN 100) - PN 10
  • 4” (DN 100) - PN 16
  • 4” (DN 100) - PN 25
  • 4” (DN 100) - PN 40

Frequency

  • 2,400 - 2,483.5 MHz License Free ISM Band

Function

  • Linear
  • Square Root

Gasket Material

  • 316 Stainless Steel (Hoop) - Gasket for Transmitter Side (Spiral)
  • PTFE Teflon (Filler) - Gasket for Transmitter Side (Spiral), Process Connector
  • Teflon-Coated 316L Stainless Steel - Capsule

Humidity

  • 0 to 100 % Relative Humidity - Ambient Humidity Limits

Length

  • 50 to 150 mm - Extension

NPT Connection

  • 1/2” NPT Female
  • 1/4” NPT Female

Nut & Bolt Material

  • Bolting: 316L Stainless Steel
  • Bolting: 660 Stainless Steel
  • Bolting: Carbon Steel (B7)

O-Ring Material

  • 316 Stainless Steel - Flushing Connection Ring
  • Buna-N

Power

  • Maximum

Power Requirement

  • 7.2 V, 19 Ah Battery
  • Lithium Thionyl Chloride Batteries

Pressure Range

  • bar: 0 to 79.98
  • Inches WC: 0 to 2,000
  • kPa: 0 to 7,998
  • psi: 0 to 1,160

Pressure Type

  • Absolute

Process Connection Style

  • Extended Typical
  • Flush Typical

Process Temperature

  • -10° to 250° C (14° to 482° F) - High Pressure Side
  • -40° to 120° C (-40° to 248° F) - Low Pressure Side

Response Time

  • 180 milliseconds - M & H Capsule

Span & Zero Adjustments

  • 0.01 % of Span Incremental Resolution - External Zero Adjustment
  • Zero can be Fully Elevated or Suppressed, within the Lower & Upper Range Limits of the Capsule - Zero Adjustment Limits

Span & Zero Effect

  • ± 0.007 % of URL - M & H Capsules (Effect on Zero)

Span Effect

  • ± 0.028 % of Span - M & H Capsules

Stability

  • ± 0.1 % of URL Per Year

Supply Pressure

  • psi: 0.38 to 14.5 (kPa: 2.7 to 100, bar: 0.026 to 1)

Temperature Effect

  • ± [0.14 % of Span + 0.028 % of URL] Per 28° C (50° F) - at Capsule H (Ambient Temperature Effects)
  • ± [0.224 % of Span + 0.056 % of URL] Per 28° C (50° F) - at Capsule M (Ambient Temperature Effects)

Update Time

  • 0.5 to 3,600 seconds - Quick Update Time
  • 100 milliseconds

Wetted Materials

  • 316 Stainless Steel - Others
  • 316L Stainless Steel - Others
  • Hastelloy C-276 - Others
  • Tantalum - Others
show more