VJR6 Isolated Single & Dual Output RTD Converter

Brand: Yokogawa Electric Corporation

The VJR6 is a compact, plug-in type RTD converter that is connected to an IEC/JIS-standard resistance temperature detector (RTD) to convert temperature signals into isolated DC current or DC voltage signals.

Specifications

Accuracy

  • ± 0.1 % of Span or 0.1° C (0.18° F), whichever is greater
  • ± 0.2 % of Span or 0.2° C (0.36° F), whichever is greater - Pt50

Approvals & Certifications

  • CE
  • EMC: EN 61326

Burn-Out

  • Downscale
  • Off
  • Time: 60 seconds
  • Upscale

Consumption

  • 2.1 W at 110 Vdc
  • 2.2 W at 24 Vdc
  • 4.2 VA at 100 Vac
  • 6.1 VA at 200 Vac

Current

  • 1 mA DC
  • 1-24 mA - Span (DC)

Electrical Connectors

  • M3 Screw Terminal

Enclosure, Body Material

  • Modified Polyphenylene Oxide

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Insulation Resistance

  • 100 megaohms Min. at 500 Vdc

Mounting

  • DIN Rail or Dedicated VJ Mounting Base (VJCE) Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-20 mA DC
  • -10-10 Vdc

Output Format

  • DC Current Signal
  • DC Voltage Signal

Power Supply Effect

  • Up to ± 0.1 % of Span for the Regulation within Allowable Range

Resistance

  • 2 to 250 kiloohms - DC Voltage Signal
  • 350 to 15,000 ohms - DC Current Signal
  • Up to ± 0.2° C (± 0.36° F) Per 10 ohms/Leadwire - Effect of Leadwire Resistance

Response Time

  • 150 milliseconds, 63 % Response (10 to 90 %)

RTD Type

  • JPt100 (JIS’89)
  • Pt100 (ITS-90: JIS’97) & (IPTS-68: JIS’89)
  • Pt50 (JIS’81)

Sensor, Probe Type

  • A 3-Wire RTD

Span - Minimum

  • 10° C (18° F)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,000 Vac/minute between Output-1 & Output-2 Terminals (Withstanding Voltage)
  • 10 mV-20 V - Span (DC)
  • 100-240 Vac/Vdc, 50/60 Hz
  • 15-30 Vdc (± 20 %)
  • 2,000 Vac/minute between Input, (Output-1 & Output-2), Power Supply & Grounding Terminals Terminals Mutually (withstanding Voltage)

Temperature Effect

  • Up to ± 0.15 % of Span Per 10° C (18° F) - Effect of Ambient Temperature Variations

Temperature Range

  • -200° to 510° C (-328° to 950° F) - JPt100 (JIS'89)
  • -200° to 649° C (-328° to 1,200.2° F) - Pt50 (JIS'81)
  • -200° to 660° C (-328° to 1,220° F) - Pt100 (IPTS-68: JIS'89)
  • -200° to 850° C (-328° to 1,562° F) - Pt100 (ITS-90: JIS'97)

Zero Offset

  • 0 to 200 % - Current Signal
  • -100 to 200 % - Voltage Signal
show more