EJX110A Differential Pressure Transmitter

Brand: Yokogawa Electric Corporation

The high performance differential pressure transmitter EJX110A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam flow as well as liquid level, density and pressure. 

EJX110A outputs a 4-20 mA DC signal corresponding to the measured differential pressure. Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral indicator or remotely monitored via BRAIN or HART communications. 

Other key features include quick response, remote set-up using communications, diagnostics and optional status output for pressure high/low alarm. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage. 

FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available.

All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified by TÜV as complying with SIL 2 for safety requirement.
Features
  • ± 0.04% Accuracy (0.025% Accuracy option available)
  • ± 0.1% per 15 years Stability
  • 90 ms Response Time
  • 3,600 psi MWP
  • Exida and TUV SIL2 / SIL3 Certified
  • Local Parameter Setting (LPS)

Output

Output

Measurement Span

Measurement Span
  • view details
  • view details
  • view details

Wetted Material

Wetted Material

Process Connection

Process Connection

Bolt & Nut Material

Bolt & Nut Material

Installation

Installation

Amplifier Housing

Amplifier Housing
  • view details
  • view details

Electrical Connection

Electrical Connection
  • view details
  • view details
  • view details

Integral Indicator

Integral Indicator

Mounting

Mounting

FM Approval

FM Approval

ATEX Approval

ATEX Approval

CSA Approval

CSA Approval
  • view details
  • view details

IECEx Approval

IECEx Approval
  • view details

Combination of Approvals

Combination of Approvals
  • view details

Painting

Painting

Exterior Parts

Exterior Parts

O-Ring

O-Ring

Lightning Protection

Lightning Protection
  • view details

Status Output

Status Output
  • view details

Oil-Prohibited Use

Oil-Prohibited Use
  • view details
  • view details
  • view details
  • view details

Fill Fluid

Fill Fluid
  • view details

Calibration Unit

Calibration Unit

Vent Size

Vent Size

Gasket Material

Gasket Material

Plating

Plating
  • view details

Output Limits & Failure Operation

Output Limits & Failure Operation
  • view details
  • view details
  • view details

Body Configuration

Body Configuration
  • view details
  • view details

Tag Plate

Tag Plate
  • view details

Data Configuration

Data Configuration

Advanced Diagnostic Functionality

Advanced Diagnostic Functionality
  • view details

European Pressure Equipment Directive

European Pressure Equipment Directive
  • view details

Material Certificate

Material Certificate

Pressure Test / Leak Test Certificate

Pressure Test / Leak Test Certificate
  • view details
  • view details
View Details
Part Number / SKU

EJX110A-DFS5J-912NB

  • Output

    4-20 mA DC with Digital Communication, BRAIN Protocol

  • Measurement Span

    0.1 to 5 kPa (0.4 to 20 inches WC)

  • Wetted Material

    Wetted Materials 1

  • Process Connection

    Without Process Connector (1/4” Female NPT on the Cover Flanges)

  • Bolt & Nut Material

    B7 Carbon Steel

  • Installation

    Horizontal Piping Type & Left Side High Pressure

  • Amplifier Housing

    Cast Aluminum Alloy

  • Electrical Connection

    1/2” Female NPT, Two Electrical Connections without Blind Plugs

  • Integral Indicator

    No Integral Indicator

  • Mounting

    304 Stainless Steel 2” Pipe Mounting, Flat Type

  • FM Approval

    Without FM Approval

  • ATEX Approval

    Without ATEX Approval

  • CSA Approval

    Without CSA Approval

  • IECEx Approval

    Without IECEx Approval

  • Combination of Approvals

    Without Combination of Approvals

  • Painting

    Polyurethane Paint

  • Exterior Parts

    Standard Materials

  • O-Ring

    Buna-N O-Ring

  • Lightning Protection

    Without Lightning Protection

  • Status Output

    No Status Output

  • Oil-Prohibited Use

    No Oil-Prohibited Use

  • Fill Fluid

    Silicone Fill Fluid

  • Calibration Unit

    kPa Calibration (kPa Unit)

  • Vent Size

    34 mm

  • Gasket Material

    PTFE Teflon

  • Plating

    No Plating on Diaphragms

  • Output Limits & Failure Operation

    No Output Limits & Failure Operation

  • Body Configuration

    No Body Configuration

  • Tag Plate

    No Tag Plate

  • Data Configuration

    Without Data Configuration

  • Advanced Diagnostic Functionality

    No Advanced Diagnostic Functionality

  • European Pressure Equipment Directive

    Without European Pressure Equipment Directive

  • Material Certificate

    Without Certificate

  • Pressure Test / Leak Test Certificate

    Without Pressure Test / Leak Test Certificate

Specifications

Span - Minimum

  • psi: 73 (MPa: 0.5, bar: 5)

BSP Connection

  • 1/2" BSPT Female
  • 1/4" BSPT Female

Communication

  • BRAIN
  • FOUNDATION Fieldbus
  • HART
  • PROFIBUS PA

Length

  • 1.33" (34 mm) - Standard Long Vent
  • 4.6" (119 mm) - Total Long Vent

Display

  • 10-Segment - User Configurable, Signal Characterizer for 4-20 mA Output
  • 5-Digits Numerical Display
  • 6-Digit Unit Display
  • Bar Graph
  • LCD Display

Operating Temperature

  • -20° to 80° C (-4° to 176° F)

Adjustment Type

  • External Zero Adjustment Screw
  • Push Button

Gasket Material

  • Fluorinated Rubber - Process Connector Gasket
  • PTFE Teflon - Process Connector Gasket, Capsule Gasket
  • Teflon-Coated 316L Stainless Steel - Capsule Gasket

Process Connection Material

  • ASTM CF-8M
  • Hastelloy C-276
  • Monel
  • Super Duplex Stainless Steel

Alarm

  • Down-Scale: -5 %, 3.2 mA DC or Less
  • Up-Scale: 110 %, 21.6 mA DC or more

Overpressure & Static Pressure Limits

  • ± 0.03 % of URL up to psi: 3,600 (kPa: 25,000, bar: 250)

Pressure Type

  • Absolute
  • Differential
  • Gauge

Enclosure, Body Material

  • Aluminum Alloy - Copper Cast
  • ASTM CF-8M Stainless Steel

Mounting Position Effect

  • Tilting up to 90° will cause Zero Shift up to 0.4 kPa

Electrical Protection

  • Lightning Protection

Approvals & Certifications

  • Leak Test
  • Material Certificate
  • Pressure Test
  • SIL 2 Capability for Single Transmitter Use, SIL 3 Capability for Dual Transmitter Use, IEC 61508: 2000
  • TÜV (Technischer Uberwachungsverein)

Fill Material

  • Fluorinated Oil - Fill Fluid
  • Silicone - Fill Fluid

Approvals & Certifications

  • ATEX Flameproof & Intrinsically Safe
  • CE
  • CSA Explosion-proof & Intrinsically Safe
  • EMC EN 61326-1 Class A, EN 61326-2-3, EN 61326-2-5
  • FM Explosion-proof & Intrinsically Safe
  • IECEx Intrinsically Safe & Flameproof
  • NAMUR NE43
  • PED 2014/68/EU
  • PED 97/23/EC

NACE & NIST

  • NACE MR-0103

O-Ring Material

  • Buna-N - Cover O-Ring
  • Fluororubber - Cover O-Ring

Diaphragm Material

  • Hastelloy C-276

Supply Pressure - Maximum

  • psi: 2,300 (MPa: 16, bar: 160) - for Capsule F, L, M, H & V
  • psi: 3,600 (kPa: 25,000, bar: 250) - for Capsule M, H & V

Temperature Effect

  • ± (0.04 % of Span + 0.009 % of URL) Per 28° C (50° F) for Capsule M - Ambient Temperature Effects
  • ± (0.04 % of Span + 0.0125 % of URL) Per 28° C (50° F) for Capsule H, V - Ambient Temperature Effects
  • ± (0.055 % of Span + 0.18 % of URL) Per 28° C (50° F) for Capsule F - Ambient Temperature Effects

Flange Material

  • ASTM CF-8M - Cover Flange
  • Hastelloy C-276 - Cover Flange
  • Monel - Cover Flange
  • Super Duplex Stainless Steel - Cover Flange

Drain, Vent Valves & Plug

  • 316 Stainless Steel - Name Plate & Tag
  • Hastelloy C-276
  • Monel
  • Super Duplex Stainless Steel

Input Impedance

  • 10 kΩ or more at 2.4 kHz - Input Impedance of Communicating Device

Fluid

  • Liquid & Gas
  • Steam

Burst Pressure

  • psi: 10,000 (kPa: 68,950, bar: 689)
  • psi: 6,800 (kPa: 46,880, bar: 468)

Ambient Temperature Range

  • -30° to 80° C (-22° to 176° F) - with LCD Display
  • -40° to 85° C (-40° to 185° F)

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Wetted Materials

  • 316L Stainless Steel
  • Hastelloy C-276 - Capsule
  • Monel - Capsule
  • Tantalum - Capsule

Diagnostics

  • Configuration Error - Self Diagnostics
  • CPU Error - Self Diagnostics
  • Hardware Failure - Self Diagnostics
  • Heat Trace Monitoring - Advanced Diagnostics
  • Impulse Line Blockage Detection - Advanced Diagnostics
  • Over-Range Error for Differential Pressure, Static Pressure & Capsule Temperature - Self Diagnostics

NPT Connection

  • 1/2" NPT Female
  • 1/4" NPT Female

Enclosure Finish

  • Polyurethane Mint Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)

Power Supply Effect

  • ± 0.005 % per Volt (From 21.6 - 32 Vdc, 350 ohms)

Output

  • 10.5 - 30 Vdc at 120 mA DC, max.
  • 3.6 - 21.6 mA
  • 3.8 - 20.5 mA - Output Signal Limits

Output Signal

  • 4-20 mA - 2-Wire

Humidity

  • 0 to 100 % RH - Ambient Humidity

Cable Material

  • Polyethylene Insulated PVC Sheathed

Zero Offset

  • External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span

Update Time

  • 360 ms - Static Pressure
  • 45 ms - Differential Pressure

Stability

  • ± 0.1 % of URL Per 10-Years (All Normal Operating Condition, Including Overpressure Effects) - M, H & V Capsules
  • ± 0.1 % of URL Per Year (All Normal Operating Condition, Including Overpressure Effects) - F Capsule

Process Temperature

  • -40° to 120° C (-40° to 248° F)

Pressure Range

  • inH₂O: -2,000 to 2,000
  • kPa: -500 to 14,000
  • mbar: -5,000 to 140,000
  • mmH₂O: -10,000 to 10,000
  • psi: -72.52 to 2,031

Vibration Effect

  • < ± 0.1 % of URL
  • < 0.1 % of URL

Mounting Position

  • Horizontal
  • Universal
  • Vertical

Static Pressure Effect

  • ± 0.02 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) for M Capsule - Effect on Zero
  • ± 0.028 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) for H, V Capsule - Effect on Zero
  • ± 0.075 % of Span Per psi: 1,000 (MPa: 6.9, bar: 69) for F, M, H & V Capsules - Span Effects
  • ± 0.1 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) for F Capsule - Effect on Zero

Supply Voltage

  • 10.5-30 Vdc - for Intrinsically Safe, Typical N, or Non-Incendive
  • 10.5-32 Vdc - for Lightning Protector
  • 10.5-42 Vdc - for General Use & Flameproof Typical
  • 16.6 Vdc - for Digital Communications, BRAIN & HART
  • 24 Vdc, up to 550 ohms Load

Electrical Connectors

  • 1/2" NPT Female
  • G 1/2" Female
  • M20 Female

Nut & Bolt Material

  • 316L Stainless Steel
  • 660 Stainless Steel
  • B7 Carbon Steel

Load

  • 0 to 1,290 ohms - for Operation
  • 0.22 μF or Less - Load Capacitance
  • 250 to 600 ohms - for Digital Communication
  • 3.3 MH or Less - Load Inductance

Distance

  • 0 to 2 Kilometers (1.25 Miles) - Communication Distance

Response Time

  • 150 ms
  • 90 ms

Mounting

  • 2" Pipe Mounting Bracket

Damping Adjustment

  • 0 to 100 seconds

Accuracy

  • ± (0.002 + 0.0019 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability) - for M Capsule
  • ± (0.005 + 0.00125 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability) - for V Capsule
  • ± (0.005 + 0.0049 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability) - for H Capsule
  • ± (0.015 + 0.01 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability) - for F Capsule
  • ± 0.04 % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability) - for F Capsule
  • ± 0.12 % of Span at 1: 1 to 5: 1 Rangedown - Total Accuracy (M Capsule)
  • ± 0.25 % of Span at 5: 1 Rangedown - Total Accuracy (M Capsule)
show more