VJRK RTD Input Limit Alarm

Brand: Yokogawa Electric Corporation

This plug-in type Limit Alarm for RTD input receives RTD signal.
Features
  • Each parameter setting can be changed using a PC (VJ77 PC-based Parameters Setting Tool) or the Handy Terminal (JHT200)
  • For the Fahrenheit display, specify the option “/DF”

Specifications

Accuracy

  • ± 0.1 % of Span

Alarm

  • 0 to 100 % of Input Range - Alarm Setting Range
  • High - Direction of Alarm Action
  • Low - Direction of Alarm Action

Burn-Out

  • Downscale
  • Off
  • Time - within 60 seconds
  • Upscale

Consumption

  • 1.9 W at 24 Vdc & 110 Vdc - Power Consumption
  • 4.1 VA at 100 Vac - Power Consumption
  • 5.1 VA at 200 Vac - Power Consumption

Current

  • Approximately 0.5 mA - Detective Current

Electrical Connectors

  • M3 Screw Terminal

Electrical Rating

  • 0.1 A at 120 Vdc - Resistive Load - Contact Rating
  • 0.5 A at 220 Vac - Resistance Load - Contact Rating
  • 1 A at 120 Vac (Resistance Load) - Contact Rating
  • 1 A at 30 Vdc - Resistive Load - Contact Rating

Enclosure, Body Material

  • Modified Polyphenylene Oxide Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Hysteresis

  • 0 to 100 % of Input Range - Hysteresis Setting Range

Indication

  • LED - Front Panel Lights

Insulation Resistance

  • 100 megaohms at 500 Vdc between Input, Output 1, Output 2, Power Supply & Grounding Rerminals Mutually

Measuring Span

  • 10° C (50° F) or more

Mounting

  • Base Mounting - VJ
  • DIN Rail Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Operating Voltages

  • 12-36 V
  • 85-264 V

Output Format

  • Relay Contact - Signal Typical

Power Supply

  • 100-240 Vac/dc (-15 %, 10 %), 50/60 Hz - Power Supply Rated & Input Voltage
  • 15-30 Vdc (± 20 %) - Power Supply Rated & Input Voltage

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuations within the Allowable Range of Each Power Supply Voltage Specification

Resistance

  • ± 2° C (0.36° F) or Less for a Change of 10 ohms / Leadwire - Effects of Leadwire Resistance
  • 1 Megaohm (During Power On) - Input Resistance
  • 10 ohms/Leadwire - Allowable Leadwire Resistance
  • 4 kiloohms (During Power Off) - Input Resistance

Resolution

  • 0.1° C, with Four Significant Digits - Setting Resolution
  • 1 second (0.2 second is to be Added to the Set Time to Prevent Wrong Operation) - Setting Resolution

Response Time

  • 450 milliseconds

RTD Type

  • JPt100 (JIS'89)
  • Pt100 (ITS-90), (JIS’89) & (IPTS-68)
  • Pt50 (JIS’81)

Sensor, Probe Type

  • IEC/JIS-Standard RTD

Supply Voltage

  • ± 4 Vdc - Max.
  • 1,000 Vac/minute - Withstand Voltage between Output 1 & Output 2 Terminals
  • 2,000 Vac/minute - Withstand Voltage between Input, (Output 1, Output 2), Power Supply & Grounding Terminals Mutually

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature

Temperature Range

  • 0° to 100° C (32° to 212° F) - Input Range
  • -200° to 660° C (-328° to 1,220° F) - Guaranteed Range

show more