FG1A/FG1V PT Converter

Brand: Yokogawa Electric Corporation

The FG1A/FG1V is a compact, front terminal connection type PT converter that converts AC voltage signals into isolated DC current or DC voltage signals.
Features
  • AC/DC Conversion is Made by Root Mean Square Value

Specifications

Accuracy

  • ± 0.2 % of Span

Consumption

  • 60 mA at 24 Vdc - Current Consumption (FG1V)
  • 90 mA at 24 Vdc - Current Consumption (FG1A)

Current

  • 1-24 mA DC - Span

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Frequency

  • 40 to 10,000 Hz - Input Frequency Range

Humidity

  • 5 to 90 % RH, Non-Condensing - Operating Humidity

Input

  • 0.5 VA or Less - Input Loss
  • 0 to 300 Vac
  • 120 % (Continuous) - Max.
  • 200 % (One Minute) - Max.

Input Signal

  • 0 to 110 Vac
  • 0 to 150 Vac

Insulation Resistance

  • 100 MΩ or more at 500 Vdc between Input, Output & Output, Power Supply & Input, Power Supply

Mounting

  • DIN Rail Mounting
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-100 mVdc
  • 0-24 mA DC
  • -10 to 10 Vdc

Power Supply

  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations

Resistance

  • 2 to 250 kΩ or more - Allowable Load Resistance for DC Voltage Output
  • 750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output

Response Time

  • 170 ms, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 10 mV-20 V - Span (DC)
  • 2,600 Vac/minute between Input & Output & Power Supply - Withstand Voltage
  • 30-300 Vac - Span
  • 500 Vac/minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation for Current Signal
  • -100 to 200 % - Zero Elevation for Voltage Signal

show more