The JUXTA FX2 Series, Computing unit (Variable/ Fixed Software Type) receives a voltage input signal, applies various computing functions to it, and outputs isolated DC current or DC voltage signals to controllers or recorders.
(± 5.0 % of Set Value) ± 1 second - Accuracy of Time Constant Setting for First Order Lag Unit & Lead Unit
(± 5.0 % of Set Value) ± 5 seconds - Accuracy of Moving Average & Time Constant Setting, Dead Time & Velocity Computation Setting
(± 5.0 % of Set Value) ± 5 %/minute - Velocity Limiter
± 0.2 % of Span
Computation Cycle
100 milliseconds
Consumption
60 mA at 24 Vdc (FX2V) - Current Consumption
82 mA at 24 Vdc (FX2A) - Current Consumption
Current
1-24 mA DC - Span
Dead Time
0 to 1,000 seconds (0-1 V) with 4 Significant Digits, Min. Unit is 1 second - Setting Range of Dead Time, Moving Average Time, Velocity Computation Time
Electrical Connectors
M4 Screw Terminal
Electrical Rating
0.2 mA DC at 9 V - Contact Detection
Enclosure, Body Material
ABS Resin
Function
Analog Memory (Variable Software Typical, with Contact Input for Holding)
Bottom Holder (Variable Software Typical, with Contact Input for Holding)
Dead Time Unit (Fixed Software Typical)
First Order Lag Unit (Fixed Software Typical)
First Order Lead Unit (Fixed Software Typical)
Moving Average Unit (Fixed Software Typical)
Peak Holder (Variable Software Typical, with Contact Input for Holding)
Program Setter (Variable Software Typical)
Programmable Unit
Velocity Computation Unit (Fixed Software Typical)
Velocity Limiter (Fixed Software Typical)
Humidity
5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity
Input
-15 to 15 Vdc - Allowable Applied Voltage
Input Signal
0-50 mA DC
Within 0-10 Vdc when Voltage is Applied (Span: 2 V or more)
Insulation Resistance
100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply
Mounting
DIN Rail Mounting
Rack-Mounted
Wall Mounted
Operating Temperature
0° to 50° C (32° to 122° F)
Output Signal
0 to 100 mVdc
0 to 24 mA DC
-10 to 10 Vdc
Power Supply
24 Vdc ± 10 %
Power Supply Effect
± 0.2 % of Span or Less of Span for Fluctuation of 24 Vdc ± 10 %
Resistance
1 Megaohm (100 kiloohms or more During Power Off) - Input Resistance
100 kiloohms or more - Contact Signal (Open)
100 to 5,000 ohms - Input Resistance
2 to 250 kiloohms or more - Allowable Load Resistance for DC Voltage Output
200 ohms or Less - Contact Signal (Close)
750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output
Response Time
500 milliseconds, 63 % Response (10 to 90 %)
Supply Voltage
1,500 Vac/minute between (Input & Output) & Power Supply - Withstand Voltage
10 mV-20 V - Span (DC)
500 Vac/minute between Output & Power Supply - Withstand Voltage
Temperature Effect
± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Ambient Temperature Effect
Time Constant