WR9A/WR9V Dew Point Converter

Brand: Yokogawa Electric Corporation

The WR9A/WR9V is a compact, front terminal connection type dew point converter that converts dew-point temperature signals into isolated DC current or DC voltage signals.
Features
  • Burnout setting, I/O adjustment and I/O monitoring can be made using the optional parameter setting tool (VJ77) or handy terminal (JHT200) 
  • Dual output and 2,000 Vac withstand voltage specifications are available 
  • For the Fahrenheit display, specify the option “/DF”

Specifications

Accuracy

  • ± 0.2 % of Span or 0.2° C (0.36° F) whichever is greater (Including Linearization Error)
  • Relative Error within ± 0.2 % between Output 1 & 2 - Dual Output

Burn-Out

  • 60 seconds or Less - Burn-Out Time
  • Down
  • Off
  • Up

Consumption

  • 10 VA at 100 Vac (WR9A) - Power Consumption
  • 55 mA at 24 Vdc (WR9V) - Current Consumption
  • 6 VA at 100 Vac (WR9V) - Power Consumption
  • 90 mA at 24 Vdc (WR9A) - Current Consumption

Current

  • Approximately 1 mA DC - Measuring Current

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Input & Power Supply, Input & Ground, Output & Power Supply, Output & Ground, & Power Supply & Ground

Measuring Range

  • -45° to 60° C (-49° to 140° F)

Mounting

  • DIN Rail Mounting
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 24 mA DC
  • 10 mV-20 V - Span (DC)
  • -10-10 Vdc
  • 1-24 mA - Span (DC)

Power Supply

  • 24 Vdc ± 10 % (DC Drive)
  • 85-264 Vac, 47 to 63 Hz (AC Drive)

Power Supply Effect

  • ± 0.1 % of Span or Less - Power Supply Voltage Fluctuations

Resistance

  • 150 ohms or Less Per Wire - Allowable Leadwire Resistance
  • 2 to 250 kiloohms or more - Allowable Load Resistance for DC Voltage Output
  • 750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output

Response Time

  • 200 milliseconds, 63 % Response (10 to 90 %)

Sensor, Probe Type

  • Ni RTD (3-Wire Typical) of Dew-Point Sensor

Span & Zero Adjustments

  • ± 1 % - Input Adjustment
  • ± 10 % - Output Adjustment

Supply Voltage

  • 1,500 Vac/minute for AC Drive - Withstand Voltage
  • 500 Vac/minute between Output & Power Supply for DC Drive - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation (Current Signal)
  • -100 to 200 % - Zero Elevation (Voltage Signal)

show more