FF1A/FF1V P/E Transducer

Brand: Yokogawa Electric Corporation

P/E Transducer converts pneumatic signals of 20 to 100 kPa, 0.2 to 1.0 kgf/cm2 or 3 to 15 psi into current or voltage signals.
Features
  • Compact Type, by Using Semi-conductor Pressure Sensor

Specifications

Accuracy

  • ± 0.2 % of Span

BSP Connection

  • 1/8” BSPT Female - Input Signal Connecting Hole

Current

  • 1-24 mA DC - Span Current Signal

Dissipation

  • 45 mA at 24 Vdc - Current Dissipation
  • 75 mA at 24 Vdc - Current Dissipation

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Plastic

Humidity

  • 5 to 90 % Relative Humidity Non-Condensing

Input

  • Less than psi: 28 (kPa: 200, bar: 2) - Permissible Input Pressure

Input Signal

  • 3 to 15 psi
  • 20 to 100 kPa
  • 0.2 to 1.0 kgf/cm²

Insulation Resistance

  • > 100 megaohms at 500 Vdc between Output to Power Supply

Media

  • Dry, Non-Corrosive Air

Mounting

  • DIN Rail Mounting
  • Rack-Mounted
  • Wall Mounted

Output Signal

  • 1-5 Vdc
  • 0-5 Vdc
  • 0-10 Vdc
  • 0-1 Vdc
  • 0-100 mVdc
  • 0-10 mVdc
  • 0-1 mA DC
  • 0-10 mA DC
  • 0-16 mA DC
  • 1-5 mA DC
  • 2-10 mA DC
  • 4-20 mA DC
  • 0-20 mA DC
  • -10 to 10 Vdc

Power Supply

  • 24 Vdc ± 10 % (Ripple Content: 5 % Peak-to-Peak or Less)

Power Supply Effect

  • < ± 0.1 % of Span for 24 Vdc ± 10 % Fluctuation - Effect of Power Voltage Fluctuation

Resistance

  • 2 to 250 kiloohms - Permissible Load Resistance for DC Voltage Output
  • 750 to 15,000 ohms - Permissible Load Resistance for DC Current Output

Span & Zero Adjustments

  • ± 5 % of Span

Supply Voltage

  • 10 mV-20 Vdc - Span Voltage Signal
  • 500 Vac / 1 Minute between Output to Power Supply - Withstand Voltage

Temperature Effect

  • < ± 0.4 % of Span for 10° C (18° F) Change - Effect of Ambient Temperature Change

Temperature Range

  • 0° to 50° C (32° to 122° F)

Zero Offset

  • 0 to 200 % - Zero Elevation for Current Signal
  • -100 to 200 % - Zero Elevation for Voltage Signal

Documentation

show more