EJX130A Differential Pressure Transmitter
Brand: Yokogawa Electric CorporationThe high performance differential pressure transmitter EJX130A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam flow as well as liquid level, density and pressure.
EJX130A outputs a 4-20 mA DC signal corresponding to the measured differential pressure. Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral indicator or remotely monitored via BRAIN or HART communications.
Other key features include quick response, remote set-up using communications, diagnostics and optional status output for pressure high/low alarm. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage.
FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available. All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified by TÜV as complying with SIL 2 for safety requirement.
Features- ± 0.04% Accuracy
- ± 0.1% Stability per 15 years
- 150 ms Response Time
- 4,500 psi MWP
- Exida and TUV SIL 2/3 Certified
- Local Parameter Setting (LPS)
Specifications
Accuracy
- ± (0.005 + 0.0035 URL/Span) % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability) - M Capsule
- ± (0.005 + 0.0049 URL/Span) % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability) - H Capsule
- ± 0.04 % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability)
Alarm
- Down-Scale: -5 %, 3.2 mA DC or Less
- Up-Scale: 110 %, 21.6 mA DC or more
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) - with LCD Display
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- Leak Test
- Material Certificate
- Pressure Test
- SIL 2 Capability for Single Transmitter Use, SIL 3 Capability for Dual Transmitter Use, IEC 61508: 2000
- TÜV (Technischer Uberwachungsverein)
Approvals & Certifications
- ATEX Flameproof & Intrinsically Safe
- CE Category III, Module H
- CSA Explosion-proof & Intrinsically Safe
- EMC EN 61326-1 Class A, Table 2, EN 61326-2-3, EN 61326-2-5
- FM Explosion-proof & Intrinsically Safe
- IECEx Intrinsically Safe & Flameproof Approval
- NAMUR NE43
- PED - 97/23/EC, 2014/68/EU
Burst Pressure
- psi: 19,100 (MPa: 132, bar: 1,320)
Cable Material
- Polyethylene Insulated PVC Sheathed
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
- PROFIBUS PA
Damping Adjustment
- 0 to 100 seconds
Diagnostics
- Configuration Error
- CPU Failure
- Hardware Failure
- Over-Range Error
Diaphragm Material
- ASTM N10276
- Hastelloy C-276
Display
- 10-Segment Signal Characterizer for 4-20 mA Output - Signal Characterizer
- 5-Digit Numerical Display
- 6-Digit Unit Display
- Bar Graph
- LCD Display
Distance
- 0 to 2 Kilometers (1.25 Miles) - Communication Distance
Drain, Vent Valves & Plug
- 316 Stainless Steel
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
Electrical Rating
- 10.5-30 Vdc, 120 mA DC, Max.
- Contact Rating: 10.5-30 Vdc, 120 mA DC, Max.
Enclosure Finish
- Anti-Corrosion Coating - Coating Change for Painting
- Polyurethane Mint-Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)
Enclosure, Body Material
- ASTM CF-8M Stainless Steel
- Low Copper Cast Aluminum Alloy
Environmental Protection
- IP66
- IP67
- NEMA 4X
Fill Material
- Fluorinated Oil
- Silicone Oil
Flange Material
- F316 Stainless Steel - Cover Flange
Fluid
- Liquid & Gas
Function
- Linear - Local Parameter Setting
- Square Root - Local Parameter Setting
Gasket Material
- Teflon-Coated 316L Stainless Steel
Humidity
- 0 to 100 % Relative Humidity - Ambient Humidity
Input Impedance
- 10 kiloohms or more at 2.4 kHz
Length
- 34 mm (Standard) - Long Vent
- Total Length: 119 mm - Long Vent
Load
- 0 to 1,290 ohms - for Operation
- 0.22 µF or Less - Load Capacitance
- 250 to 600 ohms - for Digital Communication
- 3.3 MH or Less - Load Inductance
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Name Plate & Tag, Mounting Bracket
- SCS 13A - Mounting Bracket
- SCS14A - Mounting Bracket
Mounting
- 2” Pipe Mounting Bracket
Mounting Position
- Horizontal Piping - Installation
- Universal Flange - Installation
- Vertical Piping - Installation
Mounting Position Effect
- Tilting up to 90° will cause Zero Shift up to 0.4 kPa
NACE & NIST
- NACE MR-0103
- NACE MR-0175, ISO 15156
NPT Connection
- 1/2” NPT Female
- 1/4” NPT Female
Nut & Bolt Material
- 316L Stainless Steel
- 660 Stainless Steel
- B7 Carbon Steel
O-Ring Material
- Buna-N - Cover O-Ring
- Fluororubber - Cover O-Rings
Operating Temperature
- -20° to 80° C (-40° to 176° F) - Oil-Prohibited Use & Capsule Fill Fluid
Output
- 3.6-21.6 mA - Output Range
- 4-20 mA DC - 2-Wire
Overpressure Effect
- ± 0.03 % of URL
Power Supply Effect
- ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)
Pressure Range
- Inches WC: -2,000 to 2,000
- kPa: -500 to 500
- mbar: -5,000 to 5,000
- mmWC: -10,000 to 10,000
- psi: -72.52 to 72.52
Pressure Type
- Absolute
- Differential
- Gauge
Process Connection Material
- ASTM CF-8M
Process Temperature
- -40° to 120° C (-40° to 248° F)
Response Time
- 150 milliseconds - M & H Capsules
Stability
- ± 0.1 % of URL Per 10-Years
Static Pressure
- psi: 73 (MPa: 0.5, bar: 5.03) - Min. Setting Span
Static Pressure Effect
- ± 0.02 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) - Zero Effect for Capsule M
- ± 0.028 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) - Zero Effect for Capsule H
- ± 0.075 % of Span Per psi: 1,000 (MPa: 6.9, bar: 69) - Span Effect
Supply Pressure - Maximum
- psi: 4,500 (Mpa: 32, bar: 320) - Max.
Supply Voltage
- 10.5-30 Vdc - for Intrinsically Safe, Typical N, or Non-Incendive
- 10.5-32 Vdc - for Lightning Protector
- 10.5-42 Vdc - for General Use & Flameproof Typical
- 16.6 Vdc Min. - for Digital Communications, BRAIN & HART
- 24 Vdc - up to 550 ohms Load
Temperature Effect
- ± (0.07 % of Span + 0.009 % of URL) Per 28° C (50° F) - Capsule M Ambient Temperature Effect
- ± (0.07 % of Span + 0.0125 % of URL) Per 28° C (50° F) - Capsule H Ambient Temperature Effect
Update Time
- 360 milliseconds - Static Pressure
- 45 milliseconds - Differential Pressure
Vibration Effect
- < ± 0.1 % of URL - Amplifier Housing Code 2
- < 0.1 % of URL - Amplifier Housing Code 1 & 3
Wetted Materials
- 316L Stainless Steel
- F316L Stainless Steel
Zero Offset
- External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span
Documentation
Data Sheets
Certificate
Manual
- Differential Pressure and Pressure Transmitter pdf 6.3 MB
- DPharp BRAIN Communication Type pdf 2.7 MB
- DPharp Fieldbus Communication Type pdf 3.7 MB
- DPharp HART 5/7 Communication Type pdf 12.2 MB
- DPharp PROFIBUS PA Communication Type pdf 6.2 MB
- EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual pdf 7.2 MB
- EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 622 KB
- Manual Change 22-24E: EJX-A and EJA-E Series Differential Pressure and Pressure Transmitters pdf 186 KB
- Manual Change 22-25E: EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 312 KB