EJX130A Differential Pressure Transmitter

Brand: Yokogawa Electric Corporation

The high performance differential pressure transmitter EJX130A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam flow as well as liquid level, density and pressure. 

EJX130A outputs a 4-20 mA DC signal corresponding to the measured differential pressure. Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral indicator or remotely monitored via BRAIN or HART communications. 

Other key features include quick response, remote set-up using communications, diagnostics and optional status output for pressure high/low alarm. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage. 

FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available. All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified by TÜV as complying with SIL 2 for safety requirement.
Features
  • ± 0.04% Accuracy
  • ± 0.1% Stability per 15 years
  • 150 ms Response Time
  • 4,500 psi MWP
  • Exida and TUV SIL 2/3 Certified
  • Local Parameter Setting (LPS)

Specifications

Accuracy

  • ± (0.005 + 0.0035 URL/Span) % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability) - M Capsule
  • ± (0.005 + 0.0049 URL/Span) % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability) - H Capsule
  • ± 0.04 % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability)

Alarm

  • Down-Scale: -5 %, 3.2 mA DC or Less
  • Up-Scale: 110 %, 21.6 mA DC or more

Ambient Temperature Range

  • -30° to 80° C (-22° to 176° F) - with LCD Display
  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • Leak Test
  • Material Certificate
  • Pressure Test
  • SIL 2 Capability for Single Transmitter Use, SIL 3 Capability for Dual Transmitter Use, IEC 61508: 2000
  • TÜV (Technischer Uberwachungsverein)

Approvals & Certifications

  • ATEX Flameproof & Intrinsically Safe
  • CE Category III, Module H
  • CSA Explosion-proof & Intrinsically Safe
  • EMC EN 61326-1 Class A, Table 2, EN 61326-2-3, EN 61326-2-5
  • FM Explosion-proof & Intrinsically Safe
  • IECEx Intrinsically Safe & Flameproof Approval
  • NAMUR NE43
  • PED - 97/23/EC, 2014/68/EU

Burst Pressure

  • psi: 19,100 (MPa: 132, bar: 1,320)

Cable Material

  • Polyethylene Insulated PVC Sheathed

Communication

  • BRAIN
  • FOUNDATION Fieldbus
  • HART
  • PROFIBUS PA

Damping Adjustment

  • 0 to 100 seconds

Diagnostics

  • Configuration Error
  • CPU Failure
  • Hardware Failure
  • Over-Range Error

Diaphragm Material

  • ASTM N10276
  • Hastelloy C-276

Display

  • 10-Segment Signal Characterizer for 4-20 mA Output - Signal Characterizer
  • 5-Digit Numerical Display
  • 6-Digit Unit Display
  • Bar Graph
  • LCD Display

Distance

  • 0 to 2 Kilometers (1.25 Miles) - Communication Distance

Drain, Vent Valves & Plug

  • 316 Stainless Steel

Electrical Connectors

  • 1/2” NPT Female
  • G 1/2” Female
  • M20 Female

Electrical Rating

  • 10.5-30 Vdc, 120 mA DC, Max.
  • Contact Rating: 10.5-30 Vdc, 120 mA DC, Max.

Enclosure Finish

  • Anti-Corrosion Coating - Coating Change for Painting
  • Polyurethane Mint-Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)

Enclosure, Body Material

  • ASTM CF-8M Stainless Steel
  • Low Copper Cast Aluminum Alloy

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Fill Material

  • Fluorinated Oil
  • Silicone Oil

Flange Material

  • F316 Stainless Steel - Cover Flange

Fluid

  • Liquid & Gas

Function

  • Linear - Local Parameter Setting
  • Square Root - Local Parameter Setting

Gasket Material

  • Teflon-Coated 316L Stainless Steel

Humidity

  • 0 to 100 % Relative Humidity - Ambient Humidity

Input Impedance

  • 10 kiloohms or more at 2.4 kHz

Length

  • 34 mm (Standard) - Long Vent
  • Total Length: 119 mm - Long Vent

Load

  • 0 to 1,290 ohms - for Operation
  • 0.22 µF or Less - Load Capacitance
  • 250 to 600 ohms - for Digital Communication
  • 3.3 MH or Less - Load Inductance

Materials of Construction

  • 304 Stainless Steel - Mounting Bracket
  • 316 Stainless Steel - Name Plate & Tag, Mounting Bracket
  • SCS 13A - Mounting Bracket
  • SCS14A - Mounting Bracket

Mounting

  • 2” Pipe Mounting Bracket

Mounting Position

  • Horizontal Piping - Installation
  • Universal Flange - Installation
  • Vertical Piping - Installation

Mounting Position Effect

  • Tilting up to 90° will cause Zero Shift up to 0.4 kPa

NACE & NIST

  • NACE MR-0103
  • NACE MR-0175, ISO 15156

NPT Connection

  • 1/2” NPT Female
  • 1/4” NPT Female

Nut & Bolt Material

  • 316L Stainless Steel
  • 660 Stainless Steel
  • B7 Carbon Steel

O-Ring Material

  • Buna-N - Cover O-Ring
  • Fluororubber - Cover O-Rings

Operating Temperature

  • -20° to 80° C (-40° to 176° F) - Oil-Prohibited Use & Capsule Fill Fluid

Output

  • 3.6-21.6 mA - Output Range
  • 4-20 mA DC - 2-Wire

Overpressure Effect

  • ± 0.03 % of URL

Power Supply Effect

  • ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)

Pressure Range

  • Inches WC: -2,000 to 2,000
  • kPa: -500 to 500
  • mbar: -5,000 to 5,000
  • mmWC: -10,000 to 10,000
  • psi: -72.52 to 72.52

Pressure Type

  • Absolute
  • Differential
  • Gauge

Process Connection Material

  • ASTM CF-8M

Process Temperature

  • -40° to 120° C (-40° to 248° F)

Response Time

  • 150 milliseconds - M & H Capsules

Stability

  • ± 0.1 % of URL Per 10-Years

Static Pressure

  • psi: 73 (MPa: 0.5, bar: 5.03) - Min. Setting Span

Static Pressure Effect

  • ± 0.02 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) - Zero Effect for Capsule M
  • ± 0.028 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) - Zero Effect for Capsule H
  • ± 0.075 % of Span Per psi: 1,000 (MPa: 6.9, bar: 69) - Span Effect

Supply Pressure - Maximum

  • psi: 4,500 (Mpa: 32, bar: 320) - Max.

Supply Voltage

  • 10.5-30 Vdc - for Intrinsically Safe, Typical N, or Non-Incendive
  • 10.5-32 Vdc - for Lightning Protector
  • 10.5-42 Vdc - for General Use & Flameproof Typical
  • 16.6 Vdc Min. - for Digital Communications, BRAIN & HART
  • 24 Vdc - up to 550 ohms Load

Temperature Effect

  • ± (0.07 % of Span + 0.009 % of URL) Per 28° C (50° F) - Capsule M Ambient Temperature Effect
  • ± (0.07 % of Span + 0.0125 % of URL) Per 28° C (50° F) - Capsule H Ambient Temperature Effect

Update Time

  • 360 milliseconds - Static Pressure
  • 45 milliseconds - Differential Pressure

Vibration Effect

  • < ± 0.1 % of URL - Amplifier Housing Code 2
  • < 0.1 % of URL - Amplifier Housing Code 1 & 3

Wetted Materials

  • 316L Stainless Steel
  • F316L Stainless Steel

Zero Offset

  • External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span
show more