MQ0 Analog/Pulse Transmitter

Brand: Yokogawa Electric Corporation

Model MQ0 Analog/Pulse Transmitter receives DC voltage or current signal and converts it into isolated pulse train signal.

It outputs either one of collector, voltage pulse, dry contact AC Switch or relay contact.
Features
  • Function of Low Input Cut (standard 1%) Installed, Can Set Up to 1-10%

Specifications

Accuracy

  • ± 0.1 % of Span

Current

  • 100 µA-150 mA - Span (DC)

Dissipation

  • 135 mA at 24 Vdc - Current Dissipation
  • 5 VA at 100 Vac - Power Dissipation
  • 8 VA at 200 Vac - Power Dissipation

Electrical Connectors

  • M3.5 Screw Terminal

Electrical Rating

  • 1 A at 100 Vac - Max.
  • 200 mA at 100 Vac - Max.

Enclosure, Body Material

  • ABS Plastic

Frequency

  • 0 to 4,000 Hz - Output Range
  • 0.001 to 4,000 Hz - Span

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Input

  • 0 to 100 mVdc
  • 0 to 150 mA DC
  • -10-10 Vdc

Insulation Resistance

  • 100 megaohms at 500 Vdc between Input, Output & Power Supply & Ground

Load

  • 100 Vac / 1 A, Below 100 Hz - Max.

Mounting

  • DIN Rail Mounting
  • Wall Mounted

Output

  • 24 Vdc / 140 mA - Max.
  • 30 Vdc / 200 mA - Max.
  • Open Collector

Output Format

  • Relay Contact

Power Supply

  • 12-48 Vdc
  • 85-264 Vac, 47 to 63 Hz

Power Supply Effect

  • Less than ± 0.1 % of Span for 85-264 Vac or 12-48 Vdc - Effect of Power Supply Voltage Fluctuation

Pulse Range

  • 0.1 to 500 milliseconds - Output Pulse Width (Duty 50 % Fixed)

Resistance

  • 1 Megaohm (100 kiloohms when Power Off) - Input Resistance
  • 250 to 1,000 ohms - Input Range

Response Time

  • 1.5 seconds (Span less than 100 Hz), 63 % Response (10 to 90 %)
  • 150 milliseconds (Span more than 100 Hz)

Span & Zero Adjustments

  • ± 1 % of Span - Zero Point Adjustment
  • ± 5 % of Span - Span Adjustment

Supply Voltage

  • 1,500 Vac/1 Minute between Input, Output & Power Supply & Ground - Withstand Voltage
  • 10 mV-600 Vdc - Span

Temperature Effect

  • Less than ± 0.2 % of Span for 10° C (50° F) Change

Temperature Range

  • 0° to 50° C (32° to 122° F)

Zero Offset

  • 0 to 73 % - Current Signal
  • -80 to 73 % - Voltage Signal

show more