HE579ACM300 Power & Energy Monitor

Brand: Horner

SmartBlock I/O is complementary to SmartStix I/O, providing Analog and specialty modules for CsCAN. SmartBlock is compatible with X-series OCS/RCS products (XLe, XLt, XL6, NX, QX, RX, RCX) and includes a 5-pin double CsCAN plug and Removable Field Wiring Terminals. 

SmartBlock AC Power Monitor (3-phase) provides complete power measurements, including voltage, current, power, power factor, etc.

 Direct connect up to 600 Vac (voltage), and 0 to 5 A (current) per phase.

Specifications

Brand

Accuracy

  • < 1 % of Full Scale

Applications

  • Power Monitoring

Communication

  • SmartStix I/O

Connectors

  • 5-Pin CsCan Connector

Current

  • CT Current Input: 5 A secondary

Display

  • Status LEDs

Electrical Rating

  • Measuring Rating: CAT III, Max.

Humidity

  • 5 to 95 % - Non-Condensing

Input

  • 40-600 Vac
  • PT Input (or Direct): 480 V secondary

Maximum Voltage

  • Contact Voltage: 125 Vac
  • Contact Voltage: 30 Vdc, Max.

Operating Temperature

  • 0° to 60° C (32° to 140° F)

Output

  • 0.5 A at 125 Vac
  • 1 A at 30 Vdc

Power

  • 10-30 Vdc

Power Requirement

  • Inrush Power Requirement: 14 A for 50 µs
  • Steady State Power Requirement: 60 mA at 24 Vdc

show more