FR5A/FR5V Free Range Type RTD Converter

Brand: Yokogawa Electric Corporation

The FR5A/FR5V is a compact, front terminal connection type signal conditioner that is connected to an IEC/JIS-standard resistance temperature detector (RTD) to convert temperature signals into isolated DC current or DC voltage signals.
Features
  • Selection of input type, input range setting, burnout setting, output adjustment, I/O monitoring, and loop back test can be made using the optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
  • For the Fahrenheit display, specify the option “/DF”
  • Available for the combination with Safety barrier (BARD-700)

Specifications

Accuracy

  • ± 0.1 % of Span or 0.1° C (0.18° F) whichever is greater - Pt100, JPt100
  • ± 0.2 % of Span or 0.2° C (0.36° F) whichever is greater - Pt50

Burn-Out

  • Downscale
  • Off
  • Time: 60 seconds
  • Upscale

Consumption

  • 50 mA (FR5V)
  • 65 mA at 24 Vdc (FR5A)

Current

  • 1 mA Approximately - RTD Detective Current

Electrical Connectors

  • M4 Screw Terminal

Humidity

  • 5 to 90 % Reltive Humidity (Non-Condensing) - Operating Humidity Range

Input Signal

  • A 3-Wire RTD, IEC/JIS Standard Compliant

Insulation Resistance

  • 100 MΩ min. at 500 Vdc

Mounting

  • DIN Rail
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-20 mA DC
  • 0-24 mA DC
  • -10 to 10 Vdc

Power Supply Effect

  • ± 0.1 % of Span or Less - Effect of Power Supply Voltage Fluctuations

Resistance

  • ± 0.1° C (± 0.18° F) or Less for a Change of 10 ohms - Effect of Leadwire Resistance Change
  • 150 ohms or Less Per Wire - Allowable Leadwire Resistance
  • 2 to 250 kΩ or more - Allowable Load Resistance (DC Voltage Output)
  • 750 to 15,000 ohms or Less - Allowable Load Resistance, DC Current Output

Response Time

  • 200 ms, 63 % Response (10 to 90 %)

RTD Type

  • JPt100 (JIS’89) at 100 ohms
  • Pt100 (IPTS-68: JIS’89) & (ITS-90, JIS C 1604: ’97, IEC 751: ’ 95) at 100 ohms
  • Pt50 (JIS’81) at 100 ohms

Span & Zero Adjustments

  • ± 1 % of Span - Input Adjustment
  • ± 10 % of Span - Output Adjustment

Span Effect

  • 10 mV-20 V
  • 1-24 mA DC

Supply Voltage

  • 1,500 Vac for One Minute between Input & Output & Power Supply - Withstand Voltage
  • 24 Vdc ± 10 % (Percentage Ripple 5 % Peak-to-Peak or Less)
  • 500 Vac for One Minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Temperature Range

  • -200° to 850° C (-328° to 1,562° F)

Zero Offset

  • -100 to 200 %

show more