FH2A/FH2V Free Range Type Isolator

Brand: Yokogawa Electric Corporation

The FH2A/FH2V is a compact, front terminal connection type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage signals.
Features
  • I/O Range Setting, Zero/Span Adjustment, I/O Monitoring, etc. Can be Made Using the Optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)

Specifications

Accuracy

  • ± 0.1 % of Span

Consumption

  • 50 mA - Current Consumption (FH2V)
  • 70 mA at 24 Vdc - Current Consumption (FH2A)

Current

  • 100 µA-100 mA - Span (DC)

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Input

  • 0 to 100 mA DC
  • -30 to 30 Vdc
  • 70 mA DC or Less - Max.
  • Within ± 15 Vdc - Max.

Input Signal

  • 0-50 mA DC
  • -10-10 Vdc

Insulation Resistance

  • 100 megaohms or more at 500 Vdc - between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • DIN Rail
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-10 Vdc
  • 0 to 100 mVdc
  • 0-20 mA DC
  • -10-10 Vdc

Power Supply

  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less) - Power Supply Voltage

Power Supply Effect

  • ± 0.1 % of Span or Less - Effect of Power Supply Voltage Fluctuations

Resistance

  • 1 Megaohm During Power On - Input Resistance for -10-10 Vdc & -2 to 2 Vdc
  • 10 kiloohms During Power Off - Input Resistance for -2 to 2 Vdc
  • 10 kiloohms or more - Allowable Load Resistance for 0-10 Vdc
  • 100 ohms - Input Resistance for 0-50 mA DC & 0-20 mA DC
  • 250 kiloohms or more - Allowable Load Resistance for 0 to 100 mVdc
  • 800 kiloohms During Power Off - Input Resistance for -10-10 Vdc

Response Time

  • 200 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 1 % - Input Adjustment
  • ± 10 % - Output Adjustment
  • ± 5 % of Span - in the Case of 5 V or more for Output Span

Supply Voltage

  • 0.3 to 60 Vdc - Span
  • 1,500 Vac/minute - Withstand Voltage between Input & (Output & Power Supply)
  • 500 Vac/minute - Withstand Voltage between Output & Power Supply

Temperature Effect

  • ± 0.2 % of Span or Less - Effect of Ambient Temperature Change for a Temperature Change of 10° C (18° F)

Zero Offset

  • 0 to 50 % - Zero Elevation (Input Current Signal)
  • -100 to 200 % - Zero Elevation (Output Voltage Signal)
  • -50 to 50 % - Zero Elevation (Input Voltage Signal)

show more