FH2A/FH2V Free Range Type Isolator
Brand: Yokogawa Electric CorporationThe FH2A/FH2V is a compact, front terminal connection type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage signals.
Features- I/O Range Setting, Zero/Span Adjustment, I/O Monitoring, etc. Can be Made Using the Optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
Specifications
Accuracy
- ± 0.1 % of Span
Consumption
- 50 mA - Current Consumption (FH2V)
- 70 mA at 24 Vdc - Current Consumption (FH2A)
Current
- 100 µA-100 mA - Span (DC)
Electrical Connectors
- M4 Screw Terminal
Enclosure, Body Material
- ABS Resin
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing
Input
- 0 to 100 mA DC
- -30 to 30 Vdc
- 70 mA DC or Less - Max.
- Within ± 15 Vdc - Max.
Input Signal
- 0-50 mA DC
- -10-10 Vdc
Insulation Resistance
- 100 megaohms or more at 500 Vdc - between Input & Output, Output & Power Supply, & Input & Power Supply
Mounting
- DIN Rail
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0-10 Vdc
- 0 to 100 mVdc
- 0-20 mA DC
- -10-10 Vdc
Power Supply
- 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less) - Power Supply Voltage
Power Supply Effect
- ± 0.1 % of Span or Less - Effect of Power Supply Voltage Fluctuations
Resistance
- 1 Megaohm During Power On - Input Resistance for -10-10 Vdc & -2 to 2 Vdc
- 10 kiloohms During Power Off - Input Resistance for -2 to 2 Vdc
- 10 kiloohms or more - Allowable Load Resistance for 0-10 Vdc
- 100 ohms - Input Resistance for 0-50 mA DC & 0-20 mA DC
- 250 kiloohms or more - Allowable Load Resistance for 0 to 100 mVdc
- 800 kiloohms During Power Off - Input Resistance for -10-10 Vdc
Response Time
- 200 milliseconds, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- ± 1 % - Input Adjustment
- ± 10 % - Output Adjustment
- ± 5 % of Span - in the Case of 5 V or more for Output Span
Supply Voltage
- 0.3 to 60 Vdc - Span
- 1,500 Vac/minute - Withstand Voltage between Input & (Output & Power Supply)
- 500 Vac/minute - Withstand Voltage between Output & Power Supply
Temperature Effect
- ± 0.2 % of Span or Less - Effect of Ambient Temperature Change for a Temperature Change of 10° C (18° F)
Zero Offset
- 0 to 50 % - Zero Elevation (Input Current Signal)
- -100 to 200 % - Zero Elevation (Output Voltage Signal)
- -50 to 50 % - Zero Elevation (Input Voltage Signal)