The MH1 is a plug-in type isolator that receives DC current or DC voltage signals to convert them into isolated DC current or DC voltage signals.
Features
  • Provided with power indicator lamp (RDY).

Specifications

Accuracy

  • ± 0.1 % of Span

Consumption

  • 1.5 W at 24 Vdc - Power Consumption
  • 3.2 VA at 100 Vac - Power Consumption
  • 4.4 VA at 200 Vac - Power Consumption

Current

  • 100 µA-150 mA for Span (DC) - Input Current Signal
  • 1-24 mA for Span (DC) - Output Current Signal

Electrical Connectors

  • M3.5 Screw Terminals

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Input Signal

  • 0 to 100 mVdc
  • 0 to 150 mA DC Customized
  • -300 to 300 Vdc Customized
  • Within ± 30 Vdc - Input Voltage

Insulation Resistance

  • 100 megaohms Min. at 500 Vdc between Input, Output, Power Supply & Grounding Terminals Mutually

Mounting

  • DIN Rail Mounting
  • Wall Mounting

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output Signal

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • -10 to 10 Vdc

Power Supply Effect

  • Up to ± 0.1 % of Span for the Regulation of 85-264 Vac or 12-48 Vdc - Effects of Power Line Regulation

Resistance

  • 1 Megaohm - DC Voltage Input Resistance During Power On
  • 10 kiloohms - DC Voltage Input Resistance During Power Off
  • 100 to 1,000 ohms - DC Current Input Resistance
  • 2 to 250 kiloohms Min. - DC Voltage Allowable Load Resistance
  • 750 to 15,000 ohms, Max.
  • 800 kiloohms - DC Voltage Input Resistance During Power Off

Response Time

  • 150 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 10 mV-20 V for Span (DC) - Output Voltage Signal
  • 10 mV-600 V for Span (DC) - Input Voltage Signal
  • 12-48 Vdc
  • 2,000 Vac for One Minute between Input, Output, Power Supply & Grounding Terminals Mutually - Withstanding Voltage
  • 85-264 Vac, 47 to 63 Hz

Temperature Effect

  • Up to ± 0.15 % of Span Per 10° C (18° F) - Effects of Ambient Temperature Variations

Zero Offset

  • 0 to 200 % for Output Current Signal - Zero Elevation
  • 0 to 73 % for Input Current Signal - Zero Elevation
  • -100 to 200 % for Output Voltage Signal - Zero Elevation
  • -80 to 73 % for Input Voltage Signal - Zero Elevation

Documentation