YTA310 Field Mount Temperature Transmitter

Brand: Yokogawa Electric Corporation

The YTA310 is the highly accurate temperature transmitters that accept Thermocouple, RTD, ohms or DC milivolts inputs and converts it to a 4-20 mA DC signal for transmission.

The YTA310 is a single sensor input model. The models support either BRAIN or HART communication protocol, also supports FOUNDATION fieldbus.

The YTA310 in their standard configuration, with the exception of the Fieldbus type, are certified by TÜV as complying with SIL 2 for safety requirement.
Features
  • Outstanding Performance
  • High Reliability
  • Variety of Sensor Inputs
  • Digital Communication
  • Self-diagnostics Function
  • LCD Display with Bar graph

Specifications

Accuracy

  • ± 0.02 % of Span - D/A Accuracy
  • ± 0.35 ohm - Resistance
  • ± 0.5° C (± 0.9° F) - Cold Junction Compensation Accuracy (Thermocouple Only)
  • ± 12 μV - Millivolts

Alarm

  • Down-Scale: -5 %, 3.2 mA DC or Less
  • Up-Scale: 110 %, 21.6 mA DC or more

Ambient Temperature Range

  • -30° to 80° C (-22° to 176° F) with Integral Indicator
  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • SIL 2 (Capability for Single Transmitter Use), SIL 3 (Capability for Dual Transmitter Use) & IEC 61508: 2000
  • TÜV (Technischer Uberwachungsverein)

Approvals & Certifications

  • ATEX: Intrinsically Safe, Flameproof & Dust Ignition-proof
  • CSA: Intrinsically Safe, Non-Incendive & Explosion-proof
  • EMC: EN 61326-1 Class A (Industrial Locations), EN 61326-2-3, EN 61326-2-5 (Fieldbus)
  • FM: Intrinsically Safe, Non-Incendive & Explosion-proof
  • IEC Ex: Intrinsically Safe, Flameproof & Dust Ignition-proof
  • NAMUR NE43 Compliant
  • TIIS: Flameproof

Cable Material

  • Polyethylene Insulated PVC Sheathed

Communication

  • BRAIN
  • FOUNDATION Fieldbus
  • HART

Current

  • 6,000 A - Max.

Damping Adjustment

  • 0 to 99 seconds Selectable - Damping Time Constant

Diagnostics

  • Ambient Temperature Error - Self Diagnostics
  • CPU Error - Self Diagnostics
  • EEPROM Error - Self Diagnostics
  • Loss of Input Error - Self Diagnostics

Diameter

  • Cable O.D.: 0.33” to 0.43” (8.5 to 11 mm)

Display

  • 5-Digit LCD - Numerical Display with °C, K, °F, °R, % & mV (Integral-Indicator)
  • Bar Graph (0 to 100 %) - Integral Indicator
  • Dot Matrix LCD - Integral Indicator

Distance

  • 0 to 2 Kilometers - Communication Distance

Electrical Connectors

  • 1/2” NPT Female
  • G 1/2” Female
  • M20 Female
  • M4 Screw Terminal
  • PG13.5 Female

Electrical Protection

  • Lightning Protection

Enclosure Finish

  • Deep Sea Moss Green (Munsell 0.6 GY3.1/2.0) - Coating
  • Epoxy Resin Coating
  • Polyurethan Resin Baked Finish - Coating

Enclosure, Body Material

  • SCS14A Stainless Steel (Equivalent to SUS316 Cast Stainless Steel & ASTM CF-8M)

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Humidity

  • 5 to 100 % Relative Humidity at 40° C (104° F) - Ambient Humidity Limits

Input Impedance

  • 10 kiloohms or more at 2.4 kHz - Communicating Device

Isolation

  • 500 Vdc - Input/Output / Ground Isolation

Load

  • 0 to 1,335 ohms - for Operation
  • 0.22 µF or Less - Capacitance
  • 250 to 600 ohms - for Digital Communication
  • 3.3 MH or Less - Inductance

Materials of Construction

  • 304 Stainless Steel - Data & Tag Plate, Mounting Bracket
  • 316 Stainless Steel - Data & Tag Plate, Mounting Bracket

Measuring Range

  • 0 to 2,000 ohms
  • -10 to 100 mV

Mounting

  • 2” (50.8 mm) Pipe
  • M10 x 1.5 Female 12-Deep for Mounting Bracket
  • Panel Mount (Flat)

Mounting Position

  • Horizontal
  • Vertical

Output

  • 3.68-20.8 mA
  • 4-20 mA DC - 2-Wire

Output Function

  • Manually

Power Supply Effect

  • ± 0.005 % of Calibrated Span Per Volt

Resistance

  • 1 Kiloohm or Lower - Input Signal Source Resistance (For Thermocouple, mV)
  • 10 ohms Per Wire or Lower - Input Lead Wire Resistance (For RTD, ohm)

RTD Type

  • Cu as Per SAMA RC21-4
  • JPt100 as Per JIS C1604
  • Ni120
  • Pt100 as Per IEC 751
  • Pt200 as Per IEC 751
  • Pt500 as Per IEC 751

Sensor Protection

  • Burn-Out: High (21.6 mA DC) or Low (3.6 mA DC), User Selectable

Sensor, Probe Connection

  • 2-Wire RTD or ohm
  • 3-Wire RTD or ohm
  • 4-Wire RTD or ohm
  • T/C or DC mV

Sensor, Probe Type

  • B Thermocouple as Per IEC 584
  • E Thermocouple as Per IEC 584
  • J Thermocouple as Per IEC 584
  • K Thermocouple as Per IEC 584
  • L Thermocouple as Per DIN 43710
  • N Thermocouple as Per IEC 584
  • RTD
  • R Thermocouple as Per IEC 584
  • S Thermocouple as Per IEC 584
  • T Thermocouple as Per IEC 584
  • U Thermocouple as Per DIN 43710
  • W3 Thermocouple as Per ASTM E988
  • W5 Thermocouple as Per ASTM E988

Span - Minimum

  • 10° C (18° F) - RTDs
  • 20 ohms - Resistance
  • 25° C (45° F) - Thermocouples
  • 3 mV - DC Milivolts

Stability

  • ± 0.1 % of Reading or ± 0.1° C (± 0.18° F) whichever is greater for 1-Year at 23 ± 2° C - Thermocouples
  • ± 0.1 % of Reading or ± 0.1° C (± 0.18° F) whichever is greater for 2-Years at 23 ± 2° C - RTDs
  • ± 0.2 % of Reading or ± 0.2° C (± 0.36° F) whichever is greater for 5-Years at 23° ± 2° C - RTD
  • ± 0.4 % of Reading or ± 0.4° C (± 0.72° F) whichever is greater for 5-Years at 23 ± 2° C - Thermocouples

Supply Voltage

  • 10.5-30 Vdc - for Intrinsically Safe, Typical N, Non-Incendive or Non-Sparking Typical
  • 10.5-32 Vdc - for Lightning Protector
  • 10.5-42 Vdc - for General Use & Flameproof Typical
  • 16.4 Vdc Min. - for BRAIN & HART Protocols
  • 9-32 Vdc - for Fieldbus Communication Typical

Temperature Effect

  • ± [0.0088 % of Span + 0.007 % of (Reading - LRV)]

Temperature Range

  • -200° to 2,300° C (-328° to 4,172° F) - Thermocouple Measurement Range
  • -200° to 850° C (-328° to 1,562° F) - RTD Measurement Range

Turn-On Time

  • 5 seconds Approximately

Update Time

  • Approximately 0.5 second - Single Sensor

Vibration Effect

  • 10-60 Hz, 0.21 mm - Peak Displacement
  • 60 to 2,000 Hz, 3 G
show more