Accuracy
- ± 0.02 % of Span - D/A Accuracy
- ± 0.35 ohm - Resistance
- ± 0.5° C (± 0.9° F) - Cold Junction Compensation Accuracy (Thermocouple Only)
- ± 12 μV - Millivolts
Alarm
- Down-Scale: -5 %, 3.2 mA DC or Less
- Up-Scale: 110 %, 21.6 mA DC or more
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) with Integral Indicator
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- SIL 2 (Capability for Single Transmitter Use), SIL 3 (Capability for Dual Transmitter Use) & IEC 61508: 2000
- TÜV (Technischer Uberwachungsverein)
Approvals & Certifications
- ATEX: Intrinsically Safe, Flameproof & Dust Ignition-proof
- CSA: Intrinsically Safe, Non-Incendive & Explosion-proof
- EMC: EN 61326-1 Class A (Industrial Locations), EN 61326-2-3, EN 61326-2-5 (Fieldbus)
- FM: Intrinsically Safe, Non-Incendive & Explosion-proof
- IEC Ex: Intrinsically Safe, Flameproof & Dust Ignition-proof
- NAMUR NE43 Compliant
- TIIS: Flameproof
Cable Material
- Polyethylene Insulated PVC Sheathed
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
Damping Adjustment
- 0 to 99 seconds Selectable - Damping Time Constant
Diagnostics
- Ambient Temperature Error - Self Diagnostics
- CPU Error - Self Diagnostics
- EEPROM Error - Self Diagnostics
- Loss of Input Error - Self Diagnostics
Diameter
- Cable O.D.: 0.33” to 0.43” (8.5 to 11 mm)
Display
- 5-Digit LCD - Numerical Display with °C, K, °F, °R, % & mV (Integral-Indicator)
- Bar Graph (0 to 100 %) - Integral Indicator
- Dot Matrix LCD - Integral Indicator
Distance
- 0 to 2 Kilometers - Communication Distance
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
- M4 Screw Terminal
- PG13.5 Female
Enclosure Finish
- Deep Sea Moss Green (Munsell 0.6 GY3.1/2.0) - Coating
- Epoxy Resin Coating
- Polyurethan Resin Baked Finish - Coating
Enclosure, Body Material
- SCS14A Stainless Steel (Equivalent to SUS316 Cast Stainless Steel & ASTM CF-8M)
Humidity
- 5 to 100 % Relative Humidity at 40° C (104° F) - Ambient Humidity Limits
Input Impedance
- 10 kiloohms or more at 2.4 kHz - Communicating Device
Isolation
- 500 Vdc - Input/Output / Ground Isolation
Load
- 0 to 1,335 ohms - for Operation
- 0.22 µF or Less - Capacitance
- 250 to 600 ohms - for Digital Communication
- 3.3 MH or Less - Inductance
Materials of Construction
- 304 Stainless Steel - Data & Tag Plate, Mounting Bracket
- 316 Stainless Steel - Data & Tag Plate, Mounting Bracket
Measuring Range
- 0 to 2,000 ohms
- -10 to 100 mV
Mounting
- 2” (50.8 mm) Pipe
- M10 x 1.5 Female 12-Deep for Mounting Bracket
- Panel Mount (Flat)
Output
- 3.68-20.8 mA
- 4-20 mA DC - 2-Wire
Power Supply Effect
- ± 0.005 % of Calibrated Span Per Volt
Resistance
- 1 Kiloohm or Lower - Input Signal Source Resistance (For Thermocouple, mV)
- 10 ohms Per Wire or Lower - Input Lead Wire Resistance (For RTD, ohm)
RTD Type
- Cu as Per SAMA RC21-4
- JPt100 as Per JIS C1604
- Ni120
- Pt100 as Per IEC 751
- Pt200 as Per IEC 751
- Pt500 as Per IEC 751
Sensor Protection
- Burn-Out: High (21.6 mA DC) or Low (3.6 mA DC), User Selectable
Sensor, Probe Connection
- 2-Wire RTD or ohm
- 3-Wire RTD or ohm
- 4-Wire RTD or ohm
- T/C or DC mV
Sensor, Probe Type
- B Thermocouple as Per IEC 584
- E Thermocouple as Per IEC 584
- J Thermocouple as Per IEC 584
- K Thermocouple as Per IEC 584
- L Thermocouple as Per DIN 43710
- N Thermocouple as Per IEC 584
- RTD
- R Thermocouple as Per IEC 584
- S Thermocouple as Per IEC 584
- T Thermocouple as Per IEC 584
- U Thermocouple as Per DIN 43710
- W3 Thermocouple as Per ASTM E988
- W5 Thermocouple as Per ASTM E988
Span - Minimum
- 10° C (18° F) - RTDs
- 20 ohms - Resistance
- 25° C (45° F) - Thermocouples
- 3 mV - DC Milivolts
Stability
- ± 0.1 % of Reading or ± 0.1° C (± 0.18° F) whichever is greater for 1-Year at 23 ± 2° C - Thermocouples
- ± 0.1 % of Reading or ± 0.1° C (± 0.18° F) whichever is greater for 2-Years at 23 ± 2° C - RTDs
- ± 0.2 % of Reading or ± 0.2° C (± 0.36° F) whichever is greater for 5-Years at 23° ± 2° C - RTD
- ± 0.4 % of Reading or ± 0.4° C (± 0.72° F) whichever is greater for 5-Years at 23 ± 2° C - Thermocouples
Supply Voltage
- 10.5-30 Vdc - for Intrinsically Safe, Typical N, Non-Incendive or Non-Sparking Typical
- 10.5-32 Vdc - for Lightning Protector
- 10.5-42 Vdc - for General Use & Flameproof Typical
- 16.4 Vdc Min. - for BRAIN & HART Protocols
- 9-32 Vdc - for Fieldbus Communication Typical
Temperature Effect
- ± [0.0088 % of Span + 0.007 % of (Reading - LRV)]
Temperature Range
- -200° to 2,300° C (-328° to 4,172° F) - Thermocouple Measurement Range
- -200° to 850° C (-328° to 1,562° F) - RTD Measurement Range
Update Time
- Approximately 0.5 second - Single Sensor
Vibration Effect
- 10-60 Hz, 0.21 mm - Peak Displacement
- 60 to 2,000 Hz, 3 G