DP3 Free Range Type Pulse to Analog Converter

Brand: Yokogawa Electric Corporation

The DP3 is a nest-mounting type DCS-supported pulse-to-Analog converter that receives pulse-train signals and converts them into DC voltage or DC current signals proportional the the frequency.
Features
  • Internal filter can be set to eliminate chattering (in cases where the input frequency range is up to 100 Hz, the pulse width is 3 Milliseconds or more)
  • On-site adjustment for setting the zero/span, low cut point, Input/Output monitoring etc. can be performed from the host system or a handy terminal

Specifications

Accuracy

  • Output 1: ± 0.3 % of Span
  • Output 2: within ± 0.2 % of Relative Error between Output-1 & 2

Consumption

  • 60 mA (1-5 V) at 4 Vdc - Current Consumption
  • 90 mA at 4 Vdc (4-20 mA) - Current Consumption

Current

  • 1-24 mA DC - Span

Electrical Connectors

  • M4 Screw Terminal

Frequency

  • 0 to 10,000 Hz - Input Frequency

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • Nest-Mounting

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • 10 mV-20 V - Span (DC)
  • -10 to 10 Vdc

Power

  • 0.5 W (12 Vdc Power Supply) - Rated Power
  • 2 W (24 Vdc Power Supply) - Rated Power

Power Supply

  • 24 Vdc ± 10 % (Ripple Content 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage Specification

Resistance

  • 1 Kiloohm (Selectable with Switch Inside) - Internal Load Resistance
  • 15 kiloohms or more (Contact or Voltage Pulse) - Input Resistance
  • 200 ohms (Selectable with Switch Inside) - Internal Load Resistance
  • 510 ohms (Selectable with Switch Inside) - Internal Load Resistance

Span & Zero Adjustments

  • ± 10 %

Supply Voltage

  • -1 to 8 Vdc - Low Level Voltage Pulse
  • 1,500 Vac/minute between Input & (Output & Power Supply) - Withstand Voltage
  • 2-24 Vdc - High Level Voltage Pulse
  • 500 Vac/minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature

Zero Offset

  • 0 to 200 % - Zero Elevation (Current Signal)
  • -100 to 200 % - Zero Elevation (Voltage Signal)
show more