Approvals & Certifications
Burn-Out
- 60 seconds - Max.
- Downscale
- Off
- Upscale
Consumption
- 160 mA at 24 Vdc - Current Consumption
- 5.4 VA at 100 Vac - Power Consumption
- 7.4 VA at 200 Vac - Power Consumption
Humidity
- 5 to 90 % RH, Non-Condensing - Operating Humidity
Input
- 50 % of the Overall Resistance - Input Span
Insulation Resistance
- 100 MΩ min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually
Measuring Range
- Overall Resistance from 100 to 10,000 ohms
Mounting
- DIN Rail Mounting
- Side-by-Side Multiple Mounting Base
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Power Supply Effect
- Up to ± 0.1 % of Span for a Supply Voltage Range of 85-264 Vac (47 to 63 Hz), 85-264 Vdc / 12-36 Vdc - Effect of Power Line Regulation
Resistance
- 2 to 250 kΩ - Allowable Load Resistance for Output Voltage
- 350 to 15,000 ohms - Allowable Load Resistance for Output Current
Response Time
- 150 ms for a 63 % Response (10 to 90 % Change of Range of the Final Value)
Span & Zero Adjustments
- 0 to 50 % Range of the Overall Resistance- Zero Adjustment
- 50 to 100 % Range of the Overall Resistance - Span Adjustment
Supply Voltage
- 1,000 Vac/minute between Output-1 & Output-2 Terminals - Withstanding Voltage
- 100-240 Vac/dc (-15 %, 10 %), 50/60 Hz
- 12-36 Vdc
- 15-30 Vdc (± 20 %)
- 2,000 Vac/minute between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually - Withstanding Voltage
- 85-264 Vac (47 to 63 Hz)
- 85-264 Vdc
Temperature Effect
- Up to ± 0.2 % of Span Per 10° C (18° F) - Effect of Ambient Temperature Variations
Zero Offset
- 50 % of the Overall Resistance - Zero Elevation