The DG1 is a nest-mounting type DCS-supported isolator that receives AC voltage signals, such as PT output, and converts them into various DC current or DC voltage signals.
Features
  • AC/DC conversion is made by root mean square value

Specifications

Accuracy

  • ± 0.5 % of Span - Output 1
  • Relative Error within ± 0.2 % between Output-1 & 2 - Output

Consumption

  • 60 mA at 24 Vdc (1-5 V) - Current Consumption
  • 90 mA at 24 Vdc (4-20 mA) - Current Consumption

Current

  • 1-24 mA DC - Span

Electrical Connectors

  • M4 Screw Terminal

Frequency

  • 40 to 10,000 Hz - Input Frequency

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Input

  • 0.5 VA or Less - Input Loss
  • 0 to 300 Vac
  • 120 % (Continuous) - Max.
  • 200 % (One Minute) - Max.
  • 30-300 V - Span (AC)

Input Signal

  • 0 to 110 Vac
  • 0 to 150 Vac

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • Nest-Mounting

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 24 mA DC
  • 10 mV-20 V - Span (DC)
  • -10-10 Vdc

Power Supply

  • 24 Vdc ± 10 % (Ripple Content 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage Specification

Resistance

  • 750 to 250,000 ohms - Allowable Load Resistance

Response Time

  • 250 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 2,600 Vac/minute between Input & (Output & Power Supply) - Withstand Voltage
  • 500 Vac/minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Current Signal (Zero Elevation)
  • -100 to 200 % - Voltage Signal (Zero Elevation)
show more