WH9A/WH9V Linearizer

Brand: Yokogawa Electric Corporation

The WH9A/WH9V is a compact, front terminal connection type isolator that receives non-linear signals generated by analyzers or sound level meters, and converts them into linear DC current or DC voltage signals.
Features
  • Zero/span adjustment, input/output monitoring, can be made using the optional parameter setting tool (VJ77) or handy terminal (JHT200)
  • Dual output and 2,000 Vac withstand voltage specifications are available

Specifications

Accuracy

  • ± 0.1 % of Span
  • ± 0.2 % Relative Error between Output 1 & 2 - Dual Output

Consumption

  • 5 VA at 100 Vac - Power Consumption (WH9V)
  • 50 mA at 24 Vdc - Current Consumption (WH9V)
  • 85 mA at 24 Vdc - Current Consumption (WH9A)
  • 9 VA at 100 Vac - Power Consumption (WH9A)

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Input

  • ± 9 Vdc or Less - Max.

Input Signal

  • 1-5 Vdc (Non-Linear)

Insulation Resistance

  • 100 megaohms or more at 500 Vdc

Mounting

  • DIN Rail Mounting
  • M4 Screw x 4
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • 10 mV to 20 V - Span (DC)
  • -10-10 Vdc
  • 1-24 mA DC - Span

Power Supply

  • 24 Vdc ± 10 % - DC Drive
  • 85-264 Vac, 47 to 63 Hz - AC Drive

Power Supply Effect

  • ± 0.1 % of Span or Less for Fluctuation within the Operating Range of Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations

Resistance

  • 1 Megaohm During Power On - Input Resistance
  • 100 kiloohms During Power Off - Input Resistance
  • 2 to 250 kiloohms or more - DC Voltage Allowable Load Resistance
  • 750 to 15,000 ohms or Less - DC Current Allowable Load Resistance

Response Time

  • 200 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 1 % - Input Adjustment
  • 90 to 110 % - Output Adjustment

Supply Voltage

  • 1,500 Vac/minute Withstand Voltage for AC & DC Drive
  • 500 Vac/minute Withstand Voltage for DC Drive

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation (Output Current Signal)
  • -100 to 200 % - Zero Elevation (Output Voltage Signal)

show more