WB3A/V Current Converter

Brand: Yokogawa Electric Corporation

The WB3A/WB3V is a compact, front terminal connection type AC current converter that converts AC current signals into isolated DC current or DC voltage signals.
Features
  • AC/DC conversion is made by root mean square value
  • Dual output and 2,000 Vac withstand voltage specifications are available

Specifications

Accuracy

  • ± 0.3 % of Span
  • Relative Error between Output 1 & 2 is within ± 0.2 %

Consumption

  • 6 VA at 100 Vac - Power Consumption (WB3V-2)
  • 60 mA at 24 Vdc - Current Consumption (WB3V-1)
  • 7 VA at 100 Vac - Power Consumption (WB3A-2)
  • 90 mA at 24 Vdc - Current Consumption (WB3A-1)

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Frequency

  • 40 to 1,000 Hz - Input Frequency

Humidity

  • 5 to 90 % RH, Non-Condensing

Input

  • 120 % (Continuous) - Max.
  • 200 % (One Minute) - Max.

Input Signal

  • 0 to 1,000 mA AC
  • 4-1,000 mA AC - Span

Insulation Resistance

  • 100 MΩ or more at 500 Vdc between Input & Output, Input & Power Supply, Input & Ground, Output & Power Supply, Output & Ground, & Power Supply & Ground

Mounting

  • DIN Rail Mounting
  • M4 Screw x 4
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-24 mA DC
  • 10 mV - 20 V - Span (DC)
  • -10 to 10 Vdc
  • 1-24 mA DC - Span (DC)

Power Supply

  • 24 Vdc ± 10 % (DC Drive)
  • 85-264 Vac, 47 to 63 Hz (AC Drive)

Power Supply Effect

  • ± 0.1 % of Span or Less for Fluctuation within the Operating Range of Power Supply Voltage

Resistance

  • 1 ohm or Less - Input Resistance at 100-1,000 mA AC
  • 10 ohms or Less - Input Resistance at 10 to 100 mA AC
  • 2 to 250 kΩ or more - Allowable Load Resistance for DC Voltage Output
  • 25 ohms or Less- Input Resistance at 4-10 mA AC
  • 750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output

Response Time

  • 300 ms, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,500 Vac/minute - AC & DC Drive Withstand Voltage
  • 500 Vac/minute between Output & Power Supply - DC Drive Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation (Current Signal)
  • -100 to 200 % - Zero Elevation (Voltage Signal)