EJX430A Gauge Pressure Transmitter
Brand: Yokogawa Electric CorporationThe high performance gauge pressure transmitter EJX430A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam pressure.
The EJX430A outputs a 4 to 20 mA DC signal corresponding to the measured pressure. It also features quick response, remote setup and monitoring via BRAIN or HART communications, and diagnostics.
The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage.
FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available. All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified as complying with SIL 2 for safety requirement.
Features- ± 0.04% Accuracy (0.025% Accuracy optional)
- ± 0.1% per 15 years Stability
- 90 ms Response Time
- Exida and TUV SIL 2/3 Certified
- Local Parameter Setting (LPS)
Specifications
Accuracy
- ± (0.005 + 0.0035 URL/Span) % of Span (Includes the Effects of Terminal-based Linearity, Hysteresis & Repeatability)
- ± (0.005 + 0.0049 URL/Span) % of Span (Includes the Effects of Terminal-based Linearity, Hysteresis & Repeatability)
- ± 0.04 % of Span (Includes the Effects of Terminal-based Linearity, Hysteresis & Repeatability)
Adjustment Type
- External Zero Adjustment Screw
- Push Button
Alarm
- Down-Scale: -5 %, 3.2 mA DC or Less
- Up-Scale: 110 %, 21.6 mA DC or more
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) - with LCD Display
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- Leak Test
- Material Certificate
- Pressure Test
- SIL Certification - SIL 2 Capability for Single Transmitter Use, SIL 3 Capability for Dual Transmitter Use, IEC 61508: 2000
Approvals & Certifications
- ATEX Flameproof, Intrinsically Safe
- CSA Explosion-proof & Intrinsically Safe
- EMC EN 61326-1 Class A, EN 61326-2-3, EN 61326-2-5
- FM Explosion-proof & Intrinsically Safe
- IECEx Intrinsically Safe & Flameproof Approval
- NAMUR NE43
- PED 97/23/EC
BSP Connection
- 1/2” BSPT Female
- 1/4” BSPT Female
Burst Pressure
- psi: 10,000 (kPa: 68,950, bar: 689)
Cable Material
- Polyethylene Insulated PVC Sheathed
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
- PROFIBUS PA
Damping Adjustment
- 0 to 100 seconds
Diagnostics
- Capsule Temperature
- Configuration Error
- CPU Failure
- Hardware Failure
- Over-Range Error for Pressure
- User-Configurable Process High/Low Alarm for Pressure
Diaphragm Material
- Hastelloy C-276
Display
- 5-Digit Numerical Display
- 6-Digit Unit Display
- Bar Graph
- LCD Display
Distance
- Up to 2 Kilometers
Drain, Vent Valves & Plug
- 316 Stainless Steel
- Hastelloy C-276
- Monel
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
Enclosure Finish
- Anti-Corrosion Coating
- Polyurethane Paint, Mint-Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)
Enclosure, Body Material
- ASTM CF-8M Stainless Steel
- Low Copper Cast Aluminum Alloy
Environmental Protection
- IP66
- IP67
- NEMA 4X
Fill Material
- Fluorinated Oil
- Silicone
Flange Material
- ASTM CF-8M - Cover Flange
- Hastelloy C-276 - Cover Flange & Capsule
- Monel - Cover Flange & Capsule
Gasket Material
- Fluorinated Rubber - Process Connector Gasket
- PTFE Teflon - Process Connector Gasket
- Teflon-Coated 316L Stainless Steel - Capsule Gasket
Humidity
- 0 to 100 % Relative Humidity - Ambient Humidity
Input Impedance
- 10 kiloohms or more at 2.4 kHz - Communicating Device
Length
- 4.6” (119 mm) - Total Length
Load
- 0 to 1,290 ohms - for Operation
- 0.22 µF or Less - Load Capacitance
- 250 to 600 ohms - for Digital Communication
- 3.3 MH or Less - Load Inductance
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Name Plate & Tag, Mounting Bracket
Media
- Gas
- Liquids
- Steam
Mounting
- 2” Pipe Mounting Bracket
Mounting Position
- Horizontal
- Vertical
Mounting Position Effect
- Tilting up to 90° will cause Zero Shift up to 0.4 kPa
NACE & NIST
- NACE
NPT Connection
- 1/2” NPT Female
- 1/4” NPT Female
Nut & Bolt Material
- 316L Stainless Steel
- 660 Stainless Steel
- B7 Carbon Steel
O-Ring Material
- Buna-N - Cover O-Ring
- Fluororubber - Cover O-Ring
Operating Temperature
- -20° to 80° C (-4° to 176° F)
Output
- 10.5-30 Vdc at 120 mA DC, Max.
- 3.6-21.6 mA - Output Range
- 4-20 mA DC (2-Wire)
Overpressure & Static Pressure Limits
- psi: 2,300 (MPa: 16, bar: 160) - Max.
- psi: 3,600 (MPa: 25, bar: 250) - Max.
Power Supply Effect
- ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)
Pressure Range
- bar: -1 to 160
- MPa: -0.1 to 16
- psi: -14.5 to 2,300
Pressure Type
- Gauge
Process Connection Material
- ASTM CF-8M
- Hastelloy C-276
- Monel
Process Temperature
- -40° to 120° C (-40° to 248° F)
Response Time
- 150 milliseconds - for H Capsule
- 45 milliseconds - Dead Time
- 90 milliseconds
Screw Material
- 316 Stainless Steel, Zero-Adjustment & Set Screws
Stability
- ± 0.1 % of URL for 10-Years
Supply Pressure - Maximum
- psi: 2,300 (kPa: 15,860, bar: 158.6) - for Capsule B
- psi: 500 (kPa: 3,447, bar: 34.47) - for Capsule A
- psi: 72.52 (kPa: 500, bar: 5) - for Capsule H
Supply Voltage
- 10.5-30 Vdc - for Intrinsically Safe, Typical N or Non-Incendive Typical
- 10.5-32 Vdc - for Lightning Protector
- 10.5-42 Vdc - for General Use & Flameproof Typical
- 16.6 Vdc - Min. Voltage for Digital Communications, BRAIN & HART
- 24 Vdc - up to 550 ohms Load
Temperature Effect
- ± (0.04 % of Span + 0.009 % of URL) Per 28° C (50° F) - Capsule A & B Ambient Temperature Effect
- ± (0.04 % of Span + 0.0125 % of URL) Per 28° C (50° F) - Capsule H Ambient Temperature Effect
Update Time
- 45 milliseconds - Pressure
Vibration Effect
- < ± 0.1 % of URL Per IEC 60770-1 with Low Vibration Level (10-60 Hz, 0.15 mm Displacement / 60-500 Hz 2 G)
- < 0.1 % of URL Per IEC 60770-1 with High Vibration Level (10-60 Hz, 0.21 mm Displacement / 60-2,000 Hz 3 G)
Wetted Materials
- 316L Stainless Steel - Capsule
- F316L Stainless Steel - Capsule
- Hastelloy C-276 - Capsule
- Monel - Capsule
- Tantalum - Capsule
Zero Offset
- External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span
Documentation
Data Sheets
Certificate
Manual
- Differential Pressure and Pressure Transmitter pdf 6.3 MB
- DPharp BRAIN Communication Type pdf 2.7 MB
- DPharp Fieldbus Communication Type pdf 3.7 MB
- DPharp HART 5/7 Communication Type pdf 12.2 MB
- DPharp PROFIBUS PA Communication Type pdf 6.2 MB
- EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual pdf 7.2 MB
- EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 622 KB
- Manual Change 22-24E: EJX-A and EJA-E Series Differential Pressure and Pressure Transmitters pdf 186 KB
- Manual Change 22-25E: EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 312 KB