FQ2A/FQ2V Free Range Type Pulse to Analog Converter

Brand: Yokogawa Electric Corporation

The FQ2A/FQ2V is a compact, front terminal connection type pulse-to-Analog converter that receives pulse-train signals and converts them into DC voltage or DC current signals proportional to the frequency.
Features
  • With built-in 12 V or 24 V power Supply for Pulse Transmitter Inputs
  • Input pulse Types Include Current pulse, Voltage Pulse, Non-voltage Contact and Open Collector Contact
  • I/O Range, Input Pulse Width and Low Cut Point Setting, Zero/Span Adjustment and I/O Monitoring Can be Made On-site, using the Optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
  • Internal Filter Can be Set to Eliminate Chattering (In Cases Where the Input Frequency Range is Up to 100 Hz, The Pulse Width is 3 Milliseconds or More)

Specifications

Accuracy

  • ± 0.2 % of Span

Consumption

  • 60 mA at 24 Vdc - Current Consumption (FQ2V)
  • 90 mA at 24 Vdc - Current Consumption (FQ2A)

Duty Cycle

  • 50 ± 30 % when the Input is 100 % - Duty Cycle for Input Pulse Width

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Frequency

  • 0 to 1,000 Hz

Humidity

  • 5 to 90 % RH, Non-Condensing - Operating Humidity

Input

  • Open Collector Contact

Input Signal

  • -1 to 8 V - Low Level
  • 12 Vdc ± 10 % - Transmitter Power Supply
  • 2-24 V - High Level
  • 24 Vdc ± 10 % - Transmitter Power Supply
  • Contact Pulse
  • Current Pulse
  • Voltage Pulse

Insulation Resistance

  • 100 MΩ or more at 500 Vdc between Input & Output, Output & Power Supply & Input, Power Supply

Mounting

  • DIN Rail Mounting
  • M4 Screw x 2 - Mounting Screw
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-10 Vdc, Span is 0.5 V or more
  • 0-100 mVdc, Span is 10 mV or more
  • 0-20 mA DC, Span is 2 mA or more
  • 0-5 mA DC - Span is 1 mA or more
  • -10 to 10 Vdc

Power Supply

  • 12 Vdc / 30 mA - Transmitter Power Supply
  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less)
  • 24 Vdc / 30 mA - Transmitter Power Supply

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations

Pulse Range

  • 3 ms or more - Pulse Width

Resistance

  • 10 kΩ or more - Input Resistance (Contact or Voltage Pulse)
  • 10 to 250 kΩ - Allowable Load Resistance
  • 200 to 1,000 ohms (Selectable with Switch Inside) - Input Resistance (Current Pulse)

Response Time

  • 2 Intervals of Input + 50 ms, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 10 % - Output Adjustment

Supply Voltage

  • 1,500 Vac/minute between Input, Output & Power Supply - Withstand Voltage
  • 10 mV-20 V - Span (DC)
  • 500 Vac/minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • -100 to 200 % - Zero Elevation
show more