Price
$1,335.00
CAD
Stock
100+ In Stock
- Output Signal - Measuring Transducer 4-20 mA, 2-Wire
- Measuring Range - -50° to 150° C
- Process Connection - Clamping Connection 1/4" NPT, CrNi Steel Clamping Ring
- Installation Length / Diameter - 250 mm / 6 mm
- Electrical Connection/Enclosure Rating - Cable Gland M16 x 1.5, IP 65
- Special Features of the Version - Oil- and Grease-free
Specifications
Brand
Certifications & Approvals
- CE
Enclosure Rating
- IP67
- IP65
Measuring Range
- -50° to 250° C
Process Connection
- Thread G 1/2” B
- Thread G 1/4” B
- Thread 1/2” NPT
- Thread 1/4” NPT
- Compression Fitting G 1/2” B, PTFE Ferrule
- Compression Fitting G 1/2” B, CrNi Stainless Steel Ferrule
- Compression Fitting G 1/4” B, PTFE Ferrule
- Compression Fitting G 1/4” B, CrNi Stainless Steel Ferrule
- Compression Fitting 1/2” NPT, PTFE Ferrule
- Compression Fitting 1/2” NPT, CrNi Stainless Steel Ferrule
- Compression Fitting 1/4” NPT, PTFE Ferrule
- Compression Fitting 1/4” NPT, CrNi Stainless Steel Ferrule
Insertion Length
- 25 to 350 mm
Probe Diameter
- 3 mm, 6 mm
Output Signal
- 4-20 mA, 2-Wire (RA ≤ (L+ - 10 V) / 0.028 A [Ohm])
- Pt100, 4-Wire
Electric Connection
- Cable Gland M16 x 1.5, IP67
- Cable Gland M16 x 1.5, IP65
Accuracy
- Sensor Element: Class A According to IEC 60751
- Opt. Measuring Transducer ≤ ± 0.1 % of Span