Accuracy
- 1.0 m ± 0.5 - ZMICROFLEX-C
- > 1.0 m/3.3 feet ± 0.25 % - ZMICROFLEX-CER/CIS
Ambient Temperature Range
- -40° to 70° C (-40° to 158° F)
Applications
- Chemical Industry
- Granuled
- Liquid
- Petrochemical Plants
- Sewage / Waste Water / Tapwater Treatment
Approvals & Certifications
Communication
- HART - ZMICROFLEX-CER/CIS
Deadband
- 300 mm - ZMICROFLEX-C/CIS
- 450 mm - ZMICROFLEX-CER
Diameter
- Diameter of Extension Probe: 2.6 to 23.6” (75 to 600 mm)
Display
- 4-Digital, 12 mm LCD Display
Electrical Rating
- 1 A at 24 Vdc - ZMICROFLEX-CER
Measuring Range
- 26.2 to 36 feet (8 to 11 metres)
Operating Pressure
- psi: -3.6 to 43.5 (kPa: -25 to 300, bar: -0.25 to 3)
Operating Temperature
- -30° to 70° C (-22° to 158° F)
Output
- Analog Output: 4-20 mA (750 ohms)
Sensor, Probe Material
- Transducer Material: PVDF