MP1 Pulse Repeater

Brand: Yokogawa Electric Corporation

This plug-in type pulse repeater receives contact pulse, voltage pulse or current pulse from the field and converts it into isolated transistor contact pulse or dry Contact AC switch-pulse.
Features
  • 4 Ports Isolation (Input, Output, Power Supply, Ground)
  • Can Specify Pulse Generator Power Supply to Supply 12 Vdc or 24 Vdc
  • Versatile Power Supply (100 V / 200 Vac, 24 V / 100 Vdc)
  • If it Receives Chattering Signals, Internal Input Filter (10 Milliseconds) Requirement Can be Selected Through Switch
  • Selecting of Load Resistance and Setting Input Filter Can be Made Through Front Face
  • 2,000 Vac High Voltage Proof

Specifications

Current

  • 40-60 mA - Current Control Circuit

Dissipation

  • 15 mA at 110 Vdc - Power Dissipation
  • 5 VA at 100 Vac - Current Dissipation
  • 7.5 VA at 200 Vac - Current Dissipation
  • 70 mA at 24 Vdc - Power Dissipation

Electrical Connectors

  • M3.5 Screw Terminal

Electrical Rating

  • 15 Vdc / 15 mA or more - Input

Enclosure, Body Material

  • ABS Plastic

Frequency

  • 0 to 10 kHz - Input
  • 100 Hz (Pulse Width more than 3 milliseconds or more) - Input Frequency

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Input

  • -1 to 8 Vdc - Low Level: Pulse Signal Typical
  • 2-50 Vdc - High Level: Pulse Signal Typical
  • 50 Vdc or Less - Max.

Insulation Resistance

  • > 100 megaohms at 500 Vdc between Input, Output, Power Supply, & Grounding Terminals Mutually

Load

  • 200 mA at 100 Vac - Dry Contact AC Switch: Max.
  • 200 mA at 30 Vdc - Open Collector: Max.

Mounting

  • DIN Rail Mounting
  • Wall Mounted

Output Format

  • Dry Contact AC Switch
  • Open Collector

Power Supply

  • 100/200 Vac - Versatile Power Supply
  • 12 Vdc / 30 mA, ± 10 % - Pulse Generator Power Supply
  • 170-264 Vac, 47 to 63 Hz
  • 24 Vdc / 30 mA, ± 10 % - Pulse Generator Power Supply
  • 24/100 Vdc - Versatile Power Supply
  • 85-132 Vac, 47 to 63 Hz
  • 85-150 Vdc, 47 to 63 Hz

Pulse Range

  • 40 µs Min. or Both on Time & Off Time - Input Pulse Width

Resistance

  • 1 Kiloohm - Internal Load Resistance
  • 100 kiloohms or more - Off Input: Dry Voltage Contact
  • 15 kiloohms or more - Contact or Voltage Pulse
  • 200 ohms - Internal Load Resistance
  • 200 ohms or Less - ON Input: Dry Voltage Contact
  • 500 ohms - Internal Load Resistance

Supply Voltage

  • 2 V or more - Voltage Pulse Amplitude
  • 2,000 Vac/minute between Input, Output, Power Supply & Grounding Terminals Mutually - Withstand Voltage

Temperature Range

  • 0° to 50° C (32° to 122° F)

Time Constant

  • 10 milliseconds - Input Filter

show more