EJA110A Differential Pressure Transmitter

Brand: Yokogawa Electric Corporation

The high performance differential pressure transmitter model EJA110A can be used to measure liquid, gas, or steam flow as well as liquid level, density and pressure. 

It outputs a 4-20 mA DC signal corresponding to the measured differential pressure. 

Model EJA110A also features remote setup and monitoring through communications with the BRAIN™ terminal and CENTUM CS™ or µXL™ or HART® 275 host.
Features
  • 0.065% Accuracy
  • 0.1% Stability per 5 years
  • 2,300 psi MWP

Specifications

Accuracy

  • ± 0.065 % of Span (Including the Effects of Zero-based Linearity, Hysteresis, & Repeatability)

Alarm

  • Down-Scale: -2.5 %, 3.6 mA DC or Less
  • Down-Scale: -5 %, 3.2 mA DC or Less
  • Up-Scale: 110 %, 21.6 mA DC or more

Ambient Temperature Range

  • -30° to 80° C (-22° to 176° F) - with LCD Display
  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • CSA Explosion-proof & Intrinsically Safe
  • EMC EN 61326-1 Class A, EN 61326-2-3
  • FM Explosion-proof & Intrinsically Safe
  • IEC Ex Intrinsically Safe, Typical N & Flameproof
  • NAMUR NE43
  • PED 97/23/EC

Approvals & Certifications

  • Leak Test
  • Mill Certificate
  • Pressure Test

BSP Connection

  • 1/2” BSPT Female
  • 1/4” BSPT Female

Cable Material

  • Polyethylene Insulated PVC Sheathed

Communication

  • BRAIN
  • FOUNDATION Fieldbus
  • HART
  • PROFIBUS PA

Damping Adjustment

  • 0.1 to 64 seconds in 9 Increments
  • 0.2 to 64 seconds

Diaphragm Material

  • ASTM N10276
  • Hastelloy C-276

Display

  • 5-Digit Numerical Display
  • 6-Digit Unit Display
  • Bar Graph
  • LCD Display

Distance

  • 0 to 2 Kilometers (1.25 Miles) - Communication Distance when Using CEV Polyethylene-Insulated PVC-Sheathed Cables

Drain, Vent Valves & Plug

  • Hastelloy C-276
  • Monel
  • SUS316 - Vent Plug, Name Plate & Tag

Electrical Connectors

  • 1/2” NPT Female
  • DIN 19213
  • G 1/2” Female
  • M20 Female
  • PG13.5 Female

Enclosure Finish

  • Polyurethane Paint (Munsell 0.6 GY3.1/2.0)

Enclosure, Body Material

  • Hastelloy C-276
  • Low Copper Cast Aluminum Alloy
  • Monel
  • SCS14A

Environmental Protection

  • IP67
  • NEMA 4X

Fill Material

  • Fluorinated Oil
  • Silicone Oil

Gasket Material

  • Fluorinated Rubber - Process Connector Gasket
  • PTFE Teflon - Process Connector Gasket, Capsule Gasket
  • Teflon-Coated SUS316L - Capsule Gasket

Humidity

  • 5 to 100 % Relative Humidity at 40° C (104° F) - Ambient Humidity

Input Impedance

  • 10 kiloohms or more at 2.4 kHz

Length

  • 1.33” (34 mm) - Vent

Load

  • 0 to 1,335 ohms - for Operation
  • 0.22 μF or Less - Load Capacitance
  • 250 to 600 ohms - for Digital Communication
  • 3.3 MH or Less - Load Inductance

Materials of Construction

  • SUS304 - Name Plate & Tag

Mounting

  • 2” Pipe Mounting Bracket (Flat Typical, L Typical)

Mounting Position

  • Horizontal
  • Vertical

Mounting Position Effect

  • Tilting up to 90° will cause Zero Shift up to 0.4 kPa

NACE & NIST

  • NACE MR-0175

NPT Connection

  • 1/2” NPT Female
  • 1/4” NPT Female

Nut & Bolt Material

  • SCM435
  • SUH660
  • SUS630

O-Ring Material

  • Buna-N - Cover O-Ring
  • Fluororubber - Cover O-Ring

Operating Temperature

  • -20° to 80° C (-4° to 176° F) - Oil-Prohibited Use

Output

  • 3.8-20.5 mA
  • 4-20 mA DC

Overpressure Effect

  • ± 0.03 % of URL Per psi: 2,300 (MPa: 16, bar: 160) - M, H, V Capsules

Power Supply Effect

  • ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)

Pressure Range

  • Inches WC: -2,000 to 2,000
  • kPa: -500 to 14,000
  • mbar: -5,000 to 140,000
  • mmWC: -10,000 to 10,000
  • psi: -72.52 to 2,031

Pressure Type

  • Absolute
  • Differential
  • Gauge

Process Temperature

  • -40° to 120° C (-40° to 248° F)

Response Time

  • 0.5 second, Max.
  • 120 milliseconds

Span & Zero Effect

  • ± [0.02 % of Span + 0.052 % of URL] Per psi: 500 (MPa: 3.4, bar: 34) - Zero Effect for Capsule L
  • ± 0.028 % of URL Per psi: 1,000 (MPa: 6.9, bar: 69) - Zero Effect for Capsules M, H, V

Stability

  • ± 0.1 % of URL Per 5-Years - Capsules M, H, V
  • ± 0.2 % of URL Per 1-year - Capsule L

Static Pressure Effect

  • ± [0.07 % of Span + 0.052 % of URL] Per psi: 500 (MPa: 3.4, bar: 34) - Capsule L
  • ± [0.1 % of Span + 0.028 % of URL] Per psi: 1,000 (MPa: 6.9, bar: 69) - Capsules M, H, V

Supply Pressure - Maximum

  • psi: 2,300 (MPa: 16, bar: 160)

Supply Voltage

  • 10.5-30 Vdc - for Intrinsically Safe, Typical N, Non-Incendive, or Non-Sparking Typical
  • 10.5-32 Vdc - for Lightning Protector
  • 10.5-42 Vdc - for General Use & Flameproof Typical
  • 16.4 Vdc Min. - for Digital Communications, BRAIN & HART
  • 24 Vdc, up to A 570 ohms Load

Temperature Effect

  • ± [0.07 % of Span + 0.015 % of URL] Per 28° C (50° F) - Capsule H Ambient Temperature Effect
  • ± [0.07 % of Span + 0.02 % of URL] Per 28° C (50° F) - Capsule M Ambient Temperature Effect
  • ± [0.07 % of Span + 0.03 % of URL] Per 28° C (50° F) - Capsule V Ambient Temperature Effect
  • ± [0.08 % of Span + 0.09 % of URL] Per 28° C (50° F) - Capsule L Ambient Temperature Effect

UNF/UNC Connection

  • 7/16”-20 UNF Female

Update Time

  • 0.125 second

Wetted Materials

  • Hastelloy C-276
  • Monel
  • SUS316L
  • Tantalum

Zero Offset

  • External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span
show more