Consumption
- 2.3 W at 24 Vdc - Power Consumption
- 4.6 VA at 100 Vac - Power Consumption
- 6.4 VA at 200 Vac - Power Consumption
Dead Time
- 0 to 320,000 seconds - Setting Range of Dead Time, Moving-Average Time & Computation Time
Function
- Dead Time
- First Order Lag
- First Order Lead
- Free Program
- Limiter
- Linearizer
- Moving Average
- Ratio Setter
- Uniform-Speed Response (Velocity Limiter)
- Velocity Computation
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity
Input
- ± 15 Vdc or Less - Permissible Applicable Input
- 40 mA DC or Less for Input Resistance of 250 ohms - Permissible Applicable Input
- 70 mA DC or Less for Input Resistance of 100 ohms - Permissible Applicable Input
Input Signal
- 0-10 mA DC
- -2 to 2 Vdc
- 0-50 mA DC
- -10 to 10 Vdc
Insulation Resistance
- 100 megaohms or more at 500 Vdc between Input, Output-1, Output-2, Power Supply, & Grounding Terminals Mutually
Materials of Construction
- ABS Resin (Black), UL 94 V-0 - Main Unit
- ABS Resin + Polycarbonate Resin (Black), UL 94 V-0 - Main Unit
- Modified Polyphenylene Oxide Resin, Including Glass Fiber (Black), UL 94 V-1 - Socket
- PBT Resin, Including Glass Fiber (Black), UL 94 V-0 - Main Unit
Mounting
- DIN Rail Mounting
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output Signal
- 0-100 mVdc
- 0-5 mA DC
- 4-20 mA DC
- 1-5 Vdc
- 0-20 mA DC
- -10 to 10 Vdc
- -100 to 100 mVdc
Power Supply
- 100-240 Vac (-15, 10 %) 50/60 Hz - Power Supply Rated & Input Voltage
- 15-40 Vdc (± 20 %) - Power Supply Rated & Input Voltage
Power Supply Effect
- Equal to or Less than whichever is greater, ± 0.1 % of Span or Accuracy for the Fluctuation within the Operating Range of Each Power Supply Voltage Specification
Resistance
- 1 Megaohm - Input Resistance of Voltage Signal (800 kiloohms During Power Off) for 15-40 Vdc & (10 kiloohms During Power Off) for 100-240 Vac
- 100 ohms (External Receiving Resistor) - Input Resistance of Current Signal
- 350 to 250,000 ohms - Permissible Load Resistance
- With 250 ohms Receiving Resistor
Response Time
- 500 milliseconds, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- ± 1 % of Span or More - Input Adjustment Range
- ± 5 % of Span or More - Output Adjustment
Supply Voltage
- 1,000 Vac for 1 Minute between Output-1 & Output-2 Terminals - Withstand Voltage
- 2,000 Vac for 1 Minute between Input, Output-1 & Output-2, Power Supply & Grounding Terminals Mutually - Withstand Voltage
Temperature Effect
- ± 0.15 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change