MH1D Dual Output Isolator

Brand: Yokogawa Electric Corporation

The MH1D is a dual-output, plug-in type isolator that receives DC current or DC voltage signals to convert them into isolated DC current or DC voltage signals.
Features
  • Provided with Power indicator lamp

Specifications

Accuracy

  • ± 0.1 % of Span

Consumption

  • 2.2 W at 24 Vdc - Power Consumption
  • 4.2 VA at 100 Vac - Power Consumption
  • 6.1 VA at 200 Vac - Power Consumption

Current

  • 100 µA-150 mA for Span - Input Current Signal
  • 1-24 mA DC for Span - Output Current Signal

Electrical Connectors

  • M3.5 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity Non-Condensing - Operating Humidity Range

Input

  • -300 to 300 Vdc
  • Within ± 30 Vdc - Allowable Voltage Input

Input Signal

  • 0 to 150 mA DC
  • -10 to 10 Vdc

Insulation Resistance

  • 100 megaohms Min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals

Mounting

  • DIN Rail Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output Signal

  • 0 to 24 mA DC
  • -10 to 10 Vdc

Power Supply Effect

  • Up to ± 0.1 % of Span for the Regulation of 85-264 Vac or 12-48 Vdc - Effects of Power Line Regulation

Resistance

  • 1 Megaohm (During Power On) - Input Resistance
  • 10 kiloohms (During Power Off) - Input Resistance
  • 100 to 1,000 ohms - Input Resistance
  • 2 to 250 kiloohms - DC Voltage Allowable Load Resistance
  • 350 to 15,000 ohms - DC Current Allowable Load Resistance
  • 800 kiloohms During Power Off - Input Resistance

Response Time

  • 150 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,000 Vac for One Minute between Output-1 & Output-2 Terminals - Withstanding Voltage
  • 10 mV-20 Vdc for Span - Output Voltage Signal
  • 10 mV-600 Vdc for Span - Input Voltage Signal
  • 12-48 Vdc
  • 2,000 Vac for One Minute between Input, (Output-1 & Output-2) Power Supply & Grounding Terminals - Withstanding Voltage
  • 85-264 Vac, 47 to 63 Hz

Temperature Effect

  • Up to ± 0.15 % of Span Per 10° C (18° F) - Effects of Ambient Temperature

Zero Offset

  • 0 to 200 % - Output Current Signal
  • 0 to 73 % - Input Current Signal
  • -100 to 200 % - Output Voltage Signal
  • -80 to 73 % - Input Voltage Signal