FVX110 Fieldbus Segment Indicator

Brand: Yokogawa Electric Corporation

The FVX110 is a field indicator that allows you to switch and display up to 16 indicated values for FOUNDATION fieldbus devices. Turn the scroll knob on the case to switch displays. 

No complex operation is needed in the field and you can observe the indicated values easily.

An LCD display with LED backlight and a variety of displays has increased user-friendliness and visibility.

The FVX110 offers as standard not only the functions of a field indicator, but also PID function block, Link master, and software download functions.
Features
  • Interoperability
  • Field instruments that comply with the FOUNDATION fieldbus specifications are fully interoperable; no longer is there a need for custom designed software to communicate with other devices.
  • Display of up to 16 process variables
  • Up to 16 process variables from multiple field instruments can be displayed, significantly reducing instrumentation costs. Furthermore, support of the FOUNDATION fieldbus digital communications protocol enables the display of signal data from third-party fieldbus compliant field devices.
  • Full dot-matrix LCD with LED back light
  • The back-lit full dot-matrix LCD clearly displays text and graphics such as bar graphs, a scroll bar, and icons that indicate the page turning direction and scroll knob turning direction.
  • Link master function
  • The FVX110 supports a link master function that enables backup of network management and allows local control using field devices.
  • Function blocks
  • To facilitate device diagnostics, two functions blocks each are provided for the multiple analog output (MAO), arithmetic (AR), and input selector (IS), and a single function block is provided for the following: signal characterizer (SC), integrator (IT), and PID.
  • Software download
  • With this function, it is possible to download updates or upgrades to the FVX110 software. Typical uses of this function are the addition of function blocks and diagnostics for existing devices.
  • Self-diagnosis
  • A reliable self-diagnostic function based on the NAMUR NE107 standard detects failures in the ambient temperature limit, communications, and hardware such as the LCD and amplifier assembly.

Specifications

Ambient Temperature Range

  • -20° to 70° C (-4° to 158° F)

Approvals & Certifications

  • ATEX - Flameproof & Intrinsically Safe
  • CSA - Explosion-proof & Intrinsically Safe
  • EMC - EN 61326-1 Class A, Table 2 (For use in Industrial Location), EN 61326-2-3, EN 61326-2-5 (For FOUNDATION Fieldbus)
  • FM - Explosion-proof, Intrinsically Safe & Non-Incendive
  • IEC Ex - Flameproof, Intrinsically Safe & Typical N
  • NAMUR NE 107

Communication

  • FOUNDATION Fieldbus

Consumption

  • 15 mA - Max.
  • 24 mA - Max.

Current

  • 1,000 A (1 x 40 µs) 100 times for Repeating - Lightning Protector
  • 6,000 A (1 x 40 µs) - Max.

Display

  • 5-Digits
  • 84 Column x 32 Lines Full-Dot Matrix with LED Backlight
  • Alphanumeric LCD
  • Bar Graph
  • Icons
  • LCD Display with LED Backlight
  • Page Information
  • Scroll bar
  • Scroll Direction Information
  • Squawk

Electrical Connectors

  • 1/2” NPT Female
  • G 1/2” Female
  • M20 Female

Electrical Protection

  • Lightning Protection

Enclosure Finish

  • Anti-Corrosion Coating for Coating Change - Painting
  • Polyurethane, Mint-Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)

Enclosure, Body Material

  • 316L Stainless Steel
  • ASTM CF-8M Stainless Steel

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Execution Time

  • 30 milliseconds - mAO, IS, AR, SC, IT
  • 45 milliseconds - PID

Humidity

  • 0 to 100 % Relative Humidity - Ambient Humidity Limits

Materials of Construction

  • 316 Stainless Steel - Name Plate & Tag, Wired Tag Plate
  • 316L Stainless Steel - Scroll Knob

Mounting

  • 2” Pipe Mounting Bracket

O-Ring Material

  • Buna-N - Cover O-Ring

PID Configuration

  • PID Function Block

Screw Material

  • 316 Stainless Steel

Supply Voltage

  • 10.5-32 Vdc for Intrinsically Safe Typical - Lightning Protector
  • 9-17.5 Vdc for Intrinsically Safe Typical FISCO Model
  • 9-24 Vdc for Intrinsically Safe Typical Entity Model
  • 9-32 Vdc for General Use, Flameproof Typical, Typical N, Non-Incendive, Communication Requirements & Fieldbus Communication Typical

Documentation

show more