VJQ2 Free Range Type Pulse to Analog Converter

Brand: Yokogawa Electric Corporation

The VJQ2 is a compact, plug-in pulse-to-Analog converter that receives pulse-train signal and converts it into isolated DC voltage or DC current signal. 

The transmitter can receive either voltage pulse, current pulse, voltage-free contact signal or open-collector signal.
Features
  • A Withstanding Voltage of 2,000 Vac 
  • A Switch-selectable Input Filter for Receiving Signal Carrying a Large Amount of Chatter 
  • A Wide Supply Voltage Range - Supporting Both 100 V and 200 V Power Lines of AC or DC 
  • Close Side-by-side Mounting 

Specifications

Accuracy

  • ± 0.1 % of Span

Approvals & Certifications

  • CE
  • EMC EN 61326

Consumption

  • 146 mA at 24 Vdc - Current Consumption
  • 4.5 VA at 100 Vac - Power Consumption
  • 6.3 VA at 200 Vac - Power Consumption

Current

  • 40-60 mA - Current Limiter

Electrical Connectors

  • M3 Screw Terminal

Electrical Rating

  • 15 mA at 15 Vdc - Min. Power Requirement Rating for Contact Input

Enclosure, Body Material

  • ABS Resin

Frequency

  • 0 to 10,000 Hz - Input Frequency Range

Humidity

  • 5 to 90 % RH, Non-Condensing

Input

  • 58 Vdc - Max.

Insulation Resistance

  • 100 MΩ min. at 500 Vdc between Input, Output, Power Supply & Grounding Terminals Mutually

Mounting

  • DIN Rail Mounting
  • Side-by-Side Multiple Base Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-10 Vdc with 0.5 V Span Min.
  • 0-100 mVdc with 10 mV Span min.
  • 0-20 mA DC with 2 mA Span Min.
  • 0-5 mA DC with 1 mA Span Min.
  • -10 to 10 Vdc with 10 mA Span min.

Power Supply

  • 100-240 Vac/dc (-15 %, 10 %) 56 / 60 Hz - Power Supply Voltage
  • 15-30 Vdc (± 20 %) - Power Supply Voltage
  • 30 mA at 12 Vdc - Transmitter Power Supply
  • 30 mA at 24 Vdc - Transmitter Power Supply

Power Supply Effect

  • ± 0.1 % of Span - Effects of Power Line Regulation for a Supply Voltage Range of 85-264 Vac (47 to 63 Hz), 85-264 Vdc or 12-36 Vdc

Resistance

  • 1 kΩ - Internal Load Resistor
  • 10 kΩ min. - Input Resistance for Contact & Voltage Pulses & Allowable Output Load Resistance for 0-10 Vdc
  • 10 to 250 kΩ min. - Allowable Output Load Resistance for -10-10 Vdc
  • 100 kΩ min. - Off State Input Contact Resistance
  • 200 ohms, Max.
  • 220 ohms - Internal Load Resistor
  • 250 kΩ min. - Allowable Output Load Resistance for 0 to 100 mVdc
  • 510 ohms - Internal Load Resistor

Span & Zero Adjustments

  • Within ± 10 % of Span

Supply Voltage

  • -1 to 8 Vdc - Low Level Voltage Pulse
  • 2,000 Vac for One Minute - Withstanding Voltage between Input, Output, Power Supply & Grounding Terminals Mutually
  • 2-50 Vdc - High Level Voltage Pulse & Voltage Pulse Amplitude

Temperature Effect

  • Up to ± 0.2 % of Span for a Temperature Change of 10° C (18° F) - Effects of Ambient Temperature Variations

Time Constant

  • 10 ms - Input Filter

Zero Offset

  • > 150 % - Elevation
  • -100 to 200 % - Elevation