Ambient Temperature Range
- -40° to 70° C (-40° to 158° F)
Approvals & Certifications
- ATEX Intrinsically Safe
- CE EN 61010-1
- CSA IEC 60529
- EMC EN 61326-1 Class A, EN 55011 Class A
- FM Intrinsically Safe
- IEC Ex Intrinsically Safe
Battery Life
- 1-Year - when BootStrap Time is 60 seconds at One-to-One Connection
- 4-Years - when BootStrap Time of the HART Device is 10 seconds at One-to-One Connection
- 5-Years at 5 seconds Update Time - at 4-20 mA Loop Connection
- 8-Years at 10 seconds Update Time - at 4-20 mA Loop Connection
Cable Length
- 65.61 feet (20 metres) - Max.
Communication
- Baud Rate: 9600 bit/sec
- Half-Duplex
- HART 7
- ISA100-Wireless
- Modbus RTU
- RS-485 Compliant
Current
- 10 mA - Supply Current (Power Supply to the Modbus Device)
- 12 mA - Max.
- 4 mA - Fixed Mode for HART Devices
- 50 mA - Supply Current (Power Supply to the FN110)
Diagnostics
- Inter Module Communication Failure
- Memory Error
- Power Failure
- Sensor Communication Failure
Display
- 5-Digit Numerical & Status Display
- LCD Display
Electrical Connectors
- 1/2” NPT Female - Vertical Connection
- 1/2” NPT Male with Clamp - Horizontal Connection
- 2-Wire
- 4-Wire
- 5-Pin Round Connector Dedicated
- Blind Plug - Horizontal & Vertical Connection
- G 1/2” Female - Vertical Connection
- G 1/2” Male with Clamp - Horizontal Connection
- M20 Female - Vertical Connection
- M20 Male with Clamp - Horizontal Connection
Environmental Protection
- IP66
- IP67
- NEMA 4X
- Water-Proof
Humidity
- 0 to 100 % Relative Humidity, Non-Condensing - Ambient Humidity (Operating, Storage)
Materials of Construction
- 316 Stainless Steel - Wired Tag Plate, Mounting Bracket (For Horizontal & Vertical Piping)
Operating Temperature
- -30° to 80° C (-22° to 176° F) - LCD Visible Range
- -40° to 85° C (-40° to 185° F) - Attitude up to 3,000 metres
Operating Voltages
- 16.5 V Min. - Operating Voltage of the HART Device
Power Requirement
- 2 x Primary Lithium Thionyl Chloride Batteries
- 7.2 V, 19 Ah Battery
Shock
- 50 G, 11 milliseconds - Shock Resistance
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Supply Voltage
- 18 V, Max.
- 3.5 V - Power Supply to the Modbus Device, FN110
Temperature Effect
- ± 10° C/hour (± 18° F/hour) or Less - Ambient Temperature Gradient (Operating)
- ± 20° C/hour (± 36° F/hour) or Less - Ambient Temperature Gradient (Storage)
Update Time
- 10 minutes
- 10 seconds - for Battery Life 8-Years
- 5 seconds - for Battery Life 5-Years
- 5 to 3600 seconds - HART 7
- 8 to 3600 seconds - RS-485 Modbus Protocol
Vibration
- 0.21 mm Peak-to-Peak (10-60 Hz), 3 G (60-2 kHz) - Vibration Resistance