The YPP6820 is a rugged, explosion-proof loop-powered rate/totalizer designed for demanding flow applications.
It brings modern design, easy readability, and enhanced functionality to hazardous areas around the world in a way never seen before.
Competitors have lost sight of the fact that the primary thing customers want to do with meters such as these is to look at them.
They want a meter with a display that provides the important information about their process, can be seen under varied lighting conditions, from wide angles, and from a distance.
The YPP6820 delivers all these and more. The rugged, explosion-proof enclosure and extensive agency approvals allow it to be installed virtually anywhere.
ATEX II 2 GD, Ex d IIC T6 Gb, Ex Tb IIIC T85° C Db Ta = -40° to 75° C
CE
CSA Class I, Div. 1, Groups B, C, D, Class II, Div. 1, Groups E, F, G, Class III, Div. 1, T6, Class I, Zone 1, Ex d IIC T6 Ta = -40° to 75° C
FM Explosion-proof for use in Class I, Div. 1, Groups B, C, D, Class II, Div. 1, Groups E, F, G, Class III, Div. 1, T6, Class I, Zone 1, AEx d IIC T6 Gb Zone 21, AEx Tb IIIC T85° C Ta = -40° to 75° C
IEC Ex d IIC T6 Gb, Ex Tb IIIC T85° C Db Ta = -40° to 75° C
Communication
HART
Conduit Connection
3/4” NPT
Consumption
0.2 W, Max.
0.25 W, Max.
0.5 W, Max.
0.75 W, Max.
Deadband
0 to 100 % of Full Scale
Display
14-Segment Alphanumeric Characters
-9,999 to 99,999
Alarm Indication: HI & LO Symbol is Displayed
Backlight: White
LCD Display Backlight
Lower: Seven Characters 0.40” (10.2 mm) High
Upper: 0.70”, 7-Segment, Automatic Lead Zero Blanking
Upper: Five Digits, 0,70” (17.8 mm) High
Electrical Connectors
12 to 22 AWG
Screw Terminal
Enclosure Finish
Corrosion Resistant Epoxy Coating
Enclosure, Body Material
Explosion-proof Die Cast Aluminum with Glass Window
Environmental Protection
Explosion-proof
IP66
IP68
NEMA 4X
NEMA 7
NEMA 9
Frequency
2 to 128 Hz - Pulse Ouput
64 dB at 50/60 Hz - Normal Mode Rejection
Function
Linearization
Live Input Calibration
Password Protection
Programmable Exponent
Square Root
Humidity
0 to 90 % Non-Condensing Relative Humidity
Input
2 A, Max.
4-20 mA Loop Powered
K-Factor
Programmable from 0.0001 to 99999 - Pulse Output
Linearization
Up to 32-Points
Mounting
1-1/2” to 2-1/2” NPS or DN 40 to 65 mm Pipe Mounting
May be Mounted Directly to Conduit
Pipe
Wall Mounted
Mounting Position
Horizontal
Operating Temperature
-40° to 75° C (-40° to 167° F)
Output
Open Collector
Programming
Four Internal Pushbuttons when Cover is Removed
Four SafeTouch through-glass buttons when cover is installed
Front Panel ENTER Button & Resets Output & Screen Indication - Acknowledge
Pulse Range
250 milliseconds at 2 Hz - Max.
3.9 milliseconds at 128 Hz - Min. Pulse Width
31 milliseconds at 16 Hz - Factory Default Pulse Width
Rating
Isolated Open Collector: 30 Vdc at 150 mA - Max.
Resistance
150 ohms at 20 mA without Loop Powered Backlight - Equivalent Resistance
300 ohms at 20 mA with Loop Powered Backlight - Equivalent Resistance
Rotation
90° to 270° - Display Orientation
Storage Temperature
-40° to 85° C (-40° to 185° F)
Supply Voltage
12 Vdc
24 Vdc
30 Vdc
9 Vdc
9-36 Vdc
Thermal Drift
50 ppm/°C
Update Time
Ambient -25° C: 1 second for 1 Update - Display Update Rate
Voltage Drop
3.0 Vdc at 20 mA without Loop Powered Backlight - Max.
6.0 Vdc at 20 mA with Loop Powered Backlight - Max.