WX3 mV Input/Variable Software Computing Unit

Brand: Yokogawa Electric Corporation

The JUXTA WX3 Series, Computing unit (mV Input/ Variable Software Type) receives mV input signals, applies various computing functions to them, and outputs isolated DC current or DC voltage signals to controllers or recorders.

The computation parameters, zero points, and spans can be set and modified using a Handy Terminal (JHT200).

Specifications

Accuracy

  • (± 5.0 % of Set Value) ± 1 second
  • ± 0.2 % of Span

Consumption

  • 60 mA at 24 Vdc - Current Consumption
  • 7 VA at 100 Vac - Power Consumption
  • 8.5 VA at 100 Vac - Power Consumption
  • 82 mA at 24 Vdc - Current Consumption

Current

  • 1-24 mA DC - Span

Dead Time

  • 0 to 7,990 seconds

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Input

  • -0.5 to 4 Vdc - Max.

Input Signal

  • -10 to 50 mV - Span 10 mV or more
  • -100 to 1,250 mV - Span 250 mV or more
  • -2 to 10 mV - Span 3 mV of More
  • -50 to 250 mV - Span 50 mV or more

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • DIN Rail Mounting
  • M4 Screw x 4
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • 10 mV to 20 V - Span (DC)
  • -10-10 Vdc

Power Supply

  • 24 Vdc ± 10 %
  • 85-264 Vac, 47 to 63 Hz

Power Supply Effect

  • ± 0.1 % of Span or Less - Power Supply Voltage Fluctuations

Resistance

  • 1 Megaohm (3 kiloohms or more During Power Off) - Input Resistance
  • 750 to 250,000 ohms - Output Range

Response Time

  • 500 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 1 % of Span - Input & Output Adjustment Function

Supply Voltage

  • 1,500 Vac/minute - Withstand Voltage (AC & DC Drive) between Input & Output, & Input & Power Supply
  • 500 Vac/minute - Withstand Voltage (DC Drive) between Output & Power Supply

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature

Time Constant

  • 0 to 799 seconds

Zero Offset

  • 0 to 200 % - Current Signal Zero Elevation
  • -100 to 200 % - Voltage Signal Zero Elevation
show more