The DME is a connector-connection type 16-unit mounting nest. It is available for connection with DCS Input/Output modules for the CENTUM series of Yokogawa Electric Corporation. 

This nest includes the connector for portable manipulator (Yokogawa SPBD) by each loop as standard, for emergency backup of a control unit or each converter.
Features
  • Ranges and parameters can be set using DSC2 or the JHT200, Yokogawa handy terminal (The availability depends on the model of signal conditioners)

Specifications

Communication

  • DSC2 Card
  • RS-485

Electrical Connectors

  • M3 Screws Terminal - Input/Output Cable Shield Connection
  • M4 Screw Terminal - Input/Output Signal Connection

Enclosure Finish

  • Black

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing

Input

  • Analog
  • Pulse Train Input

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input, Output, Power Supply, Ground, & CN1-CN2

Mounting

  • M5 Screws x 4
  • Nest-Mounting
  • Rack-Mounted
  • Wall Mounted

Mounting Position

  • Horizontal

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output Format

  • Analog Output

Power Supply

  • 24 Vdc ± 10 %

Supply Voltage

  • 1,500 Vac/minute between Input & (Power Supply & Ground & CN1-CN2) - Withstand Voltage
  • 500 Vac/minute between Power Supply, Ground & CN1-CN2 - Withstand Voltage
show more