FQ2P Free Range Type Analog to Pulse Converter

Brand: Yokogawa Electric Corporation

The FQ2P is a compact, front terminal connection type Analog-to-pulse converter that converts DC current or DC voltage signals into pulse-train signals.
Features
  • I/O range, output pulse width, and low cut point setting, zero/span adjustment and I/O monitoring can be made on-site, using the optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)

Specifications

Accuracy

  • ± 0.1 % of Span

Consumption

  • 60 mA at 24 Vdc - Current Consumption

Current

  • 1-100 mA DC - Span

Duty Cycle

  • 50 ± 10 %

Enclosure, Body Material

  • ABS Resin

Frequency

  • 0 to 1,000 Hz - Output Fequency

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Input

  • 0 to 100 mA DC
  • -30 to 30 Vdc
  • 70 mA DC or Less - Max.
  • Within ± 15 Vdc - Max.

Input Signal

  • 0-50 mA DC
  • -10 to 10 Vdc

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input & Output, Output & Power Supply & Input & Power Supply

Load

  • 240 Vac / 200 mA - Max.
  • 30 Vdc / 200 mA - Max.

Mounting

  • DIN Rail Mounting
  • M4 Screw
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output Format

  • Contactless AC/DC Switch
  • Open Collector

Power Supply

  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuations within the Operating Range of Power Supply Voltage Specification

Pulse Range

  • 0.1 to 500 milliseconds - Pulse Width Setting Range (Fixed Pulse Width)

Resistance

  • 1 Megaohm - Input Resistance During Power On
  • 100 kiloohms - Input Resistance During Power Off
  • 100 ohms - Input Resistance

Span & Zero Adjustments

  • ± 1 % - Input Adjustment
  • ± 10 % - Output Adjustment

Supply Voltage

  • 1,500 Vac/minute between Input & (Output & Power Supply) - Withstand Voltage
  • 3-60 Vdc - Span
  • 500 Vac/minute between Output & Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for Ambient Temperature Change of 10° C (18° F)

Zero Offset

  • 0 to 50 % - Current Signal Zero Elevation
  • -50 to 50 % - Voltage Signal Zero Elevation
show more