WHRA/WHRV Reverse Output Type Isolator

Brand: Yokogawa Electric Corporation

The WHRA/WHRV is a compact, front terminal connection type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage signals.
Features
  • 0 to 100% of the input signals are reversed and output
  • Dual output and 2,000 Vac withstand voltage specifications are available

Specifications

Accuracy

  • ± 0.1 % of Span
  • ± 0.2 % Relative Error between Output 1 & 2 - Dual Output

Consumption

  • 10 VA at 100 Vac - Power Consumption (WHRA-2)
  • 102 mA at 24 Vdc - Current Consumption (WHRA-1)
  • 6 VA at 100 Vac - Power Consumption (WHRV-2)
  • 80 mA at 24 Vdc - Current Consumption (WHRV-1)

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Input

  • ± 30 Vdc or Less - Max.

Input Signal

  • 0 to 100 mVdc
  • 0 to 150 mA DC
  • 10 mV-600 Vdc - Span
  • 100 μA-150 mA DC - Span
  • -300 to 300 Vdc

Insulation Resistance

  • 100 megaohms or more at 500 Vdc

Mounting

  • DIN Rail Mounting
  • M4 Screw x 4
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • 10 mV to 20 V - Span (DC)
  • -10-10 Vdc
  • 1-24 mA DC - Span

Power Supply

  • 24 Vdc ± 10 % (DC Drive)
  • 85-264 Vac, 47 to 63 Hz (AC Drive)

Power Supply Effect

  • ± 0.1 % of Span or Less for Fluctuation within the Operating Range of Power Supply Voltage Specification

Resistance

  • 1 Megaohm During Power On - Input Resistance for DC Voltage Input
  • 100 kiloohms During Power Off - Input Resistance for DC Voltage Input
  • 100 to 1,000 ohms - Input Resistance for DC Current Input
  • 2 to 250 kiloohms or more - Allowable Load Resistance for DC Voltage Output
  • 750 to 15,000 ohms or Less - Allowable Load Resistance for DC Current Output

Response Time

  • 150 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,500 Vac/minute - Withstand Voltage for AC Drive, DC Drive
  • 500 Vac/minute - Withstand Voltage for DC Drive

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation (Output Current Signal)
  • 0 to 73 % - Zero Elevation (Input Current Signal)
  • -100 to 200 % - Zero Elevation (Output Voltage Signal)
  • -80 to 73 % - Zero Elevation (Input Voltage Signal)
show more