VJH7 Multifunction Isolator

Brand: Yokogawa Electric Corporation

This plug-in type isolator converts DC current or DC voltage signal into isolated DC current or DC voltage signal.
Features
  • DC voltage signal, communication output (RS485), or alarm output (2 relay contacts) is selectable as output-2.
  • Incorporation of microcomputer allows I/O adjustment, I/O monitoring, and loopback test output through PC-based Parameters Setting Tool (VJ77 sold separately) or Handy Terminal (JHT200 sold separately). 

Specifications

Accuracy

  • ± 0.1 % of Span

Alarm

  • 0 to 100 % of Input Range - Alarm Setting Range
  • 0 to 999 seconds - Setting Range
  • High/Low

Approvals & Certifications

  • CAN/CSA C22.2 No. 61010-1
  • CE EN 61326-1
  • EMC
  • KC
  • UL 61010-1

Communication

  • 2-Wire Half-Duplex (Start-Stop Synchronization, Non-procedural)
  • Baud Rate: 1,200, 2,400, 4,800, 9,600 bit/sec
  • Data Length: 7-bits, 8-bits
  • EIA RS-485
  • LADDER Communication
  • Modbus ASCII/RTU
  • PC-Link Communication Protocol
  • PC-Link with Sum
  • Stop Bit: 1-bit, 2-bits

Display

  • Front LED Lights at Excitation, 2 LEDs - Alarm Operation Display

Dissipation

  • 2.6 W at 24 Vdc & 110 Vdc - Power Dissipation
  • 5 VA at 100 Vac - Power Dissipation
  • 6.7 VA at 200 Vac - Power Dissipation

Distance

  • 3,937 feet (1,200 metres) - Max.

Electrical Connectors

  • M3 Screw Terminal

Electrical Contacts

  • Normally Closed - Output 2
  • Normally Open

Electrical Rating

  • 30 Vdc at 1 A - Contact Capacity

Enclosure, Body Material

  • Modified Polyphenylene Oxide

Frequency

  • 50/60 Hz - for Power Supply Input, Rated Voltage

Humidity

  • 5 to 90 % RH, Non-Condensing

Hysteresis

  • 3 % (Alarm-1/2)

Input

  • -1 to 1 V (L Range), Span is Under 0.5 V
  • -10-10 V (H Range), Span is Under 5 V
  • 1-5 Vdc
  • -5 to 5 V (M Range), Span is Under 2.5 V

Input Signal

  • 0-50 mA DC, Span is 5 mA or more
  • -10-10 Vdc, Span is 0.1 V or more

Insulation Resistance

  • 100 MΩ at 500 Vdc between Input, Output-1, Output-2, Power Supply & Ground Mutually

Measurement Accuracy

  • Within ± 20 % of the Range During Testing

Mounting

  • Base Mounting - VJ Mounting
  • DIN Rail Mounting
  • Wall Mounted

Output

  • 0-100 mVdc
  • 0-20 mA DC
  • 1-5 Vdc
  • 4-20 mA DC

Output Format

  • Relay Contact - Signal Typical for Alarm Output

Power Supply

  • 100-240 Vac/dc (-15 %, 10 %) 50/60 Hz - Power Supply Input, Rated Voltage
  • 15-30 Vdc (± 20 %) - Power Supply Input, Rated Voltage

Power Supply Effect

  • ± 0.1 % or Less of Span for 15-30 Vdc (± 20 %), 100-240 Vac/dc - Effect of Power Supply Voltage Fluctuation

Relay Output

  • 2 Relays

Resistance

  • 1 MΩ (100 kΩ when Power Off) - DC Voltage Signal for Input Resistance
  • 1 ohm or Less - Output Resistance
  • 100 ohms (Shunt Resistor) - DC Current Signal for Input Resistance
  • 2 kΩ or more - Permissible Load Resistance for Output 1 & 2
  • 350 ohms or Less - Permissible Load Resistance for Output 2
  • 500 kΩ or more - Output Resistance
  • 750 ohms or Less - Permissible Load Resistance for Output 1

Resolution

  • 0.1 %, 4 Significant Digits - Setting Resolution
  • 1 second - Setting Resolution

Response Time

  • 200 ms, 63 % Response (10 to 90 %) - Response Speed
  • 350 ms (Input Change 10 to 90 %, Alarm Setting Point 50 %) - Alarm Output

Supply Voltage

  • 1,000 Vac/minute between Output-1 & Output-2, Input & Output-2 at Alarm Output - Withstand Voltage
  • 2,000 Vac/minute between Input, (Output-1, Output-2), Power Supply & Ground Mutually - Withstand Voltage

Temperature Effect

  • ± 0.2 % or Less of Span for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Temperature Range

  • 0° to 50° C (32° to 122° F)

show more