Alarm
- Down-Scale: -2.5 %, 3.6 mA DC or Less
- Down-Scale: -5 %, 3.2 mA DC or Less
- Up-Scale: 110 %, 21.6 mA DC or more
Ambient Temperature Range
- -30° to 60° C (-22° to 140° F) - with Integral Indicator
- -40° to 60° C (-40° to 140° F) - General Use Typical
Approvals & Certifications
- CSA - Explosion-proof & Intrinsically Safe Approval
- EMC EN 61326-1 Class A, Table 2, EN 61326-2-3
- FM - Explosion-proof & Intrinsically Safe Approval
- IECEx - Intrinsically Safe, Typical N & Flameproof Approval
- NAMUR NE43 Compliant
- PED 97/23/EC
- TIIS - Flameproof & Intrinsically Safe Approval
Approvals & Certifications
- Leak Test
- Mill Certificate
- Pressure Test
Cable Material
- Polyethylene Insulated PVC Sheathed
Capillary Length
- 3.3 to 32.8 feet (1 to 10 metres)
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
- PROFIBUS PA
Damping Adjustment
- 0.2 to 64 seconds - Set in 9 Increments
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20
- PG13.5
Enclosure Finish
- Deep Sea Moss Green (Munsell 0.6 GY3.1/2.0)
- Epoxy Resin-Baked Coating
- Polyurethan Resin Baked Finish
Enclosure, Body Material
- Cast Aluminum Alloy - Amplifier Housing
- JIS SCS14A Stainless Steel - Amplifier Housing
Fill Material
- Ethylene Glycol
- Fluorinated Oil
- Silicone Oil
Flange Material
- JIS S25C
- JIS SCA14A - Cover Flange
- JIS SCM435 - Cover Flange Bolts Material
- JIS SUS304
- JIS SUS316
- JIS SUS630 - Cover Flange Bolts Material
Flange Size - 3” (DN 80)
- 3” (DN 80) - 150# ANSI/JPI
- 3” (DN 80) - 300# ANSI/JPI
- 3” (DN 80) - JIS 10K
- 3” (DN 80) - JIS 20K
- 3” (DN 80) - PN 10
- 3” (DN 80) - PN 16
- 3” (DN 80) - PN 25
- 3” (DN 80) - PN 40
Flange Size - 4” (DN 100)
- 4” (DN 100) - 150# ANSI/JPI
- 4” (DN 100) - 300# ANSI/JPI
- 4” (DN 100) - JIS 10K
- 4” (DN 100) - JIS 20K
- 4” (DN 100) - PN 10
- 4” (DN 100) - PN 16
- 4” (DN 100) - PN 25
- 4” (DN 100) - PN 40
Fluid Specific Gravity
- 0.94 to 1.09 - Silicone Oil
- 1.09 - Ethylene Glycol
- 1.90 to 1.92 - Fluorinated Oil
Humidity
- 5 to 100 % Relative Humidity (At 40° C) - Ambient Humidity
Input Impedance
- 10 kiloohms or more at 2.4 kHz
Load
- 0.22 µF or Less - Load Capacitance
- 250 to 600 ohms - Digital Communication
- 3.3 MH or Less - Load Inductance
Materials of Construction
- JIS 304 Stainless Steel - Tag Plate
- JIS 316 Stainless Steel - Tag Plate
Mounting
- 2” (50.8 mm) Pipe - Transmitter
- Flange Mount - Diaphragm Seals
Output
- 4-20 mA DC, 2-Wire System with Digital Communication
Power Supply Effect
- ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)
Pressure Range
- bar: -5 to 5
- Inches WC: -2,000 to 2,000
- kPa: -500 to 500
- mmWC: -10,000 to 10,000
- psi: -72.52 to 72.52
Process Temperature
- -50° to 300° C (-58° to 572° F)
Screw Material
- 316 Stainless Steel - Zero-Adjustment Screw & Set Screws
Static Pressure Effect
- Total Shift: ± 0.14 % / 0.98 MPa (10 kgf/cm²)
- Zero Shift: ± 0.1 % / 0.98 MPa (10 kgf/cm²)
Supply Pressure
- psia: 0.38 (kPa: 2.7, bar: 0.027)
Supply Voltage
- 10.5-28 Vdc - for TIIS Intrinsically Safe Typical
- 10.5-30 Vdc - for Intrinsically Safe, Typical N, Non-Incendive, or Non-Sparking Typical
- 10.5-32 Vdc - for Lightning Protector
- 10.5-42 Vdc - for General Use & Flameproof Typical
- 16.4-42 Vdc - Communication Line
Temperature Effect
- ± 1.4 %/50° C (122° F) - Total Shift Ambient Temperature Effect
Wetted Materials
- JIS 304 Stainless Steel PVC Sheathed - Protection Tube
- JIS 316 Stainless Steel - Pipe, Capillary Tube
Zero Offset
- 0.01 % of Span - Continuously Adjustable Resolution