FV1A/V Manual Setter

Brand: Yokogawa Electric Corporation

The FV1A/FV1V is a compact, front terminal connection type manual setter that outputs arbitrarily linearized DC current or DC voltage signals by changing set-volume.
Features
  • Available as a Transmitter for a Loop Back Test On-site 
  • Addition/Subtraction of I/O Signals Can be Performed in Combination with an Isolator 

Specifications

Accuracy

  • ± 0.1 % of Span (For Monitor Output)

Consumption

  • 50 mA - Current Consumption (FV1V)
  • 90 mA at 24 Vdc - Current Consumption (FV1A)

Current

  • 1-24 mA DC - Span

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Insulation Resistance

  • 100 megaohms at 500 Vdc between Output & Monitor Output, Power Supply

Mounting

  • DIN Rail Mounting
  • M4 Screw x 2 - Mounting Screw
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0-1 Vdc (0 to 100 %) - Monitor Output Signal Range
  • 0 to 100 mVdc
  • 0 to 24 mA DC
  • -10 to 10 Vdc

Power Supply

  • 24 Vdc ± 10 % (Percentage Ripple is 5 % Peak-to-Peak or Less)

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations

Resistance

  • 1 ohm or Less - Monitor Output Resistance
  • 2 kiloohms or more - Monitor Output Allowable Load Resistance
  • 2 to 250 kiloohms - Voltage Output: Allowable Load Resistance
  • 750 to 15,000 ohms - Current Output: Allowable Load Resistance

Supply Voltage

  • 10 mV-20 Vdc - Span
  • 500 Vac/minute between Output & Monitor Output, Power Supply - Withstand Voltage

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200 % - Zero Elevation for Current Signal
  • -100 to 200 % - Zero Elevation for Voltage Signal

show more