Approvals & Certifications
Consumption
- 2.1 W at 110 Vdc - Power Consumption
- 2.2 W at 24 Vdc - Power Consumption
- 4.2 VA at 100 Vac - Power Consumption
- 6.1 VA at 200 Vac - Power Consumption
Current
- 100 µA-150 mA for Span (DC) - Input Current Signal
- 1-24 mA for Span (DC) - Output Current Signal
Enclosure, Body Material
- Modified Polyphenylene Oxide
Humidity
- 5 to 90 % RH, Non-Condensing - Operating Humidity Range
Input
- ± 30 Vdc - Allowable Input Voltage
- 0 to 100 mVdc
- 0 to 150 mA DC
- -300 to 300 Vdc
Insulation Resistance
- 100 MΩ min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually
Mounting
- Base Mounting (VJCE) - Dedicated VJ Mounting
- DIN Rail Mounting
- Wall Mounting
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0-100 mVdc
- 0-24 mA DC
- -10 to 10 Vdc
Power Supply
- 100-240 Vac/dc (-15 %, 10 %) 50/60 Hz - Supply Rated & Input Voltage Range
- 15-30 Vdc (± 20 %) - Supply Rated & Input Voltage Range
Power Supply Effect
- Up to ± 0.1 % of Span for the Regulation within Allowable Range of Each Supply Voltage Range - Effects of Power Line Regulation
Resistance
- 1 MΩ - DC Voltage Input Resistance During Power-On
- 10 kΩ - DC Voltage Input Resistance During Power Off
- 100 to 1,000 ohms - DC Current Input Resistance
- 2 to 250 kΩ min. - DC Voltage Allowable Load Resistance
- 350 to 15,000 ohms, Max.
- 800 kΩ - DC Voltage Input Resistance During Power Off
Response Time
- 150 ms, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- -5 to 5 % - Zero Adjustment
- 95 to 105 % - Span Adjustment
Supply Voltage
- 1,000 Vac for One Minute between Output-1 & Output-2 Terminals - Withstanding Voltage
- 10 mV-20 V for Span (DC) - Output Voltage Signal
- 10 mV-600 V for Span (DC) - Input Voltage Signal
- 2,000 Vac for One Minute between Input, (Output-1 & Output-2), Power Supply & Grounding Terminals Mutually - Withstanding Voltage
Temperature Effect
- Up to ± 0.15 % of Span Per 10° C (18° F) - Effects of Ambient Temperature Variations
Zero Offset
- 0 to 200 % for Output Current Signal - Zero Elevation
- 0 to 73 % for Input Current Signal - Zero Elevation
- -100 to 200 % for Output Voltage Signal - Zero Elevation
- -80 to 73 % for Input Voltage Signal - Zero Elevation