MVTK Digital Limit Alarm

Brand: Yokogawa Electric Corporation

This plug-in type Digital Limit Alarm for thermocouple input receives thermocouple signal. 

It is equipped with Active color PV display (PV display color changing function).
Features
  • Either 2 Points of Alarms (Relay Transfer Contact [1a1b], 2 Points) or 4 Points of Alarms (Relay NO Contact, 4 Points) can be selected
  • An alarm status in the event of an alarm can be recognized
  • Equipped with easy-to-see large LED Display as standard
  • Using the economical mode enables the low power consumption operation (Normal Operation: approximately 0.5 W, 1 VA)
  • Input range and each parameter setting can be changed by the operation keys on the front panel
  • Can be Equipped with Monitor Output (1-5 Vdc, 4-20 mA DC or RS-485 Communication)

Specifications

Accuracy

  • ± 0.1 % ± 1-Digit of Instrument Input Range Span - Input Display & Alarm Action Point Setting Accuracy
  • ± 0.1 % of Output Span
  • ± 1° C (± 1.8° F) at 25° C (77° F) ± 15° C (27° F) - Reference Junction Compensation (Thermocouple Typical K, E, J, T, B, N, W3, W5)
  • ± 2° C (± 3.6° F) at 25° C (77° F) ± 15° C (27° F) - Reference Junction Compensation (Thermocouple Typical R, S)

Adjustment Type

  • Factory Set (Pre-Set)

Burn-Out

  • Burn-Out Time: 60 seconds or Less
  • Downscale
  • Off
  • Upscale

Communication

  • Baud Rate: 1,200, 2,400, 4,800 or 9,600 bit/sec
  • Data Length: 7-bits, 8-bits
  • LADDER Communication
  • Modbus ASCII/RTU
  • PC-Link Communication Protocol
  • PC-Link with Sum
  • RS-485 Modbus Communication Protocol
  • Stop Bit: 1-bit, 2-bits

Consumption

  • 0.5 W, 1 VA Approximately - Normal Operation Using the Economical Mode
  • 2.5 W at 110 Vdc - Power Consumption
  • 2.7 W at 24 Vdc - Power Consumption
  • 4.2 VA at 100 Vac - Power Consumption
  • 5.4 VA at 200 Vac - Power Consumption

Display

  • 0.35” (9 mm) Character Height - Data Display
  • 0.53” (13.5 mm) Character Height - PV (Measured Value) Display
  • 4-Digit
  • 7-Segment
  • LED Display: Green (Data Display) & Red/Green (PV)

Distance

  • 1,200 metres - Max.

Electrical Connectors

  • M3.5 Screw Terminal for Input/Output & Power Supply

Electrical Rating

  • 0.1 A at 120 Vdc - Resistive Load
  • 0.5 A at 220 Vac - Resistive Load
  • 1 A at 120 Vac
  • 1 A at 30 Vdc

Enclosure, Body Material

  • ABS Resin (Black) UL 94 V-0

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range

Indication

  • Alarm Status LEDs (2 or 4 Orange LEDs)

Input

  • ± 4 Vdc - Max.

Insulation Resistance

  • 100 megaohms at 500 Vdc between Inputs, Alarm Outputs, Power Supply & Monitor Output Mutually

Materials of Construction

  • Glass Fiber (Black), UL 94 V-1 - Socket
  • Modified Polyphenylene Oxide Resin - Socket

Mounting

  • DIN Rail Mounting
  • Plug-In Typical - Construction
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 1-5 Vdc
  • 4-20 mA DC - Analog Output

Output Format

  • Relay Output

Power Supply Effect

  • ± 0.1 % of Span or Less for the Fluctuations within the Allowable Range - Effect of Power Supply Fluctuation

Relay Operation

  • Energized or De-Energized Under Normal Condition - High-Low Limit Alarm (PV, Deviation)

Resistance

  • ± 15 µV or Less for a Change of 100 ohms - Effect of Leadwire Resistance Change
  • 1 Megaohm (During Power On) - Input Resistance
  • 2 kiloohms or more - Allowable Load Resistance (For 1-5 Vdc)
  • 350 ohms or Less - Allowable Load Resistance (For 4-20 mA DC)
  • 4 kiloohms (During Power Off) - Input Resistance
  • 500 ohms or Less - Allowable Leadwire Resistance

Resolution

  • 1 second - Setting Resolution
  • 1-Digit - Setting Resolution

Response Time

  • 500 milliseconds

Sensor, Probe Type

  • B Thermocouple (RH, ITS-90)
  • E Thermocouple (CRC, ITS-90)
  • J Thermocouple (IC, ITS-90)
  • K Thermocouple (CA, ITS-90)
  • N Thermocouple (ITS-90)
  • R Thermocouple (ITS-90)
  • S Thermocouple (ITS-90)
  • T Thermocouple (CC, ITS-90)
  • W3 Thermocouple (ASTM E988)
  • W5 Thermocouple (ASTM E988)

Supply Voltage

  • 1,000 Vac/minute between (Alarm Outputs 1 & 4) & (Alarm Outputs 2 & 3) & between Inputs & Monitor Output - Withstand Voltage
  • 100-240 Vac/dc (-15 %, +10 %), 50/60 Hz
  • 2,000 Vac/minute between Inputs (Alarm Outputs 1, 2, 3, 4), Monitor Output & Power Supply Mutually - Withstand Voltage
  • 24 Vdc ± 10 %

Temperature Effect

  • ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Temperature Range

  • -200° to 2,270° C (-328° to 4,118° F)

show more