Approvals & Certifications
Consumption
- 113 mA at 24 Vdc - Current Consumption
- 3.1 VA at 100 Vac - Power Consumption
- 4.3 VA at 200 Vac - Power Consumption
Current
- 40-60 mA - Current Limiter
Electrical Contacts
- Normally Closed - for Output 2
Frequency
- 0 to 10 kHz - Input Frequency Range
Humidity
- 5 to 90 % Relative Humidity Non-Condensing - Operating Humidity
Input
- -1 to 8 Vdc - for Low Level
- 2-50 Vdc - for High Level
- 58 Vdc - Max.
Insulation Resistance
- 100 megaohms Min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually
Mounting
- DIN Rail Mounting
- Side-by-Side Multiple Mounting Base
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 100 Vac / 200 mA for Contactless AC Switch
- 30 Vdc / 200 mA for Large Current Open Collector
- 30 Vdc / 30 mA for Small Current Open Collector
Power Supply
- 12 Vdc / 30 mA - Transmitter Power Supply
- 15 Vdc / 15 mA - Power Supply for Contact Input Signal
- 24 Vdc / 30 mA - Transmitter Power Supply
Power Supply Effect
- 12-36 Vdc - Effect of Power Line Regulation
- 85-264 Vac, 47 to 63 Hz - Effect of Power Line Regulation
- 85-264 Vdc - Effect of Power Line Regulation
Pulse Range
- 3 milliseconds - Pulse Width
- 40 µs Min. - Input Pulse Width for Both ON & OFF State Durations
Resistance
- 1 Kiloohm - Internal Load Resistor
- 100 kiloohms Min. - Contact Resistance for OFF-state Input
- 15 kiloohms Min. - Input Resistance for Contact & Voltage Pulses
- 200 ohms, Max.
- 220 ohms - Internal Load Resistor
- 510 ohms - Internal Load Resistor
Supply Voltage
- 1,000 Vac for One Minute between Output-1 & Output-2 Terminals - Withstanding Voltage
- 100-240 Vac/dc (-15 %, 10 %), 50/60 Hz
- 15-30 Vdc (± 20 %)
- 2,000 Vac for One Minute between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually - Withstanding Voltage
Time Constant
- Approximately 10 milliseconds for an Input Filter