MXS Universal Computing Unit

Brand: Yokogawa Electric Corporation

This plug-in type universal computing unit receives DC current or DC voltage signals, applies various computing functions to them, and then converts them into isolated DC current or DC voltage signals.
Features
  • The optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200) can be used for the setting changes of various parameters such as computing functions or input/output ranges, the setting changes of programs, and the test outputs
  • The operation indicating lamp shows the operation status, abnormalities in a setting etc
  • Without a setting tool such as Handy Terminal etc., outputs can be adjusted using the switches on the front panel

Specifications

Accuracy

  • ± 0.05 %
  • ± 0.1 % of Span

Computation Cycle

  • 100 milliseconds

Consumption

  • 2.3 W at 24 Vdc - Power Consumption
  • 4.6 VA at 100 Vac - Power Consumption
  • 6.4 VA at 200 Vac - Power Consumption

Dead Time

  • 0 to 320,000 seconds - Setting Range of Dead Time, Moving-Average Time & Computation Time

Electrical Connectors

  • M3.5 Screw Terminal

Function

  • Dead Time
  • First Order Lag
  • First Order Lead
  • Free Program
  • Limiter
  • Linearizer
  • Moving Average
  • Ratio Setter
  • Uniform-Speed Response (Velocity Limiter)
  • Velocity Computation

Humidity

  • 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity

Input

  • ± 15 Vdc or Less - Permissible Applicable Input
  • 40 mA DC or Less for Input Resistance of 250 ohms - Permissible Applicable Input
  • 70 mA DC or Less for Input Resistance of 100 ohms - Permissible Applicable Input

Input Signal

  • 0-10 mA DC
  • -2 to 2 Vdc
  • 0-50 mA DC
  • -10 to 10 Vdc

Insulation Resistance

  • 100 megaohms or more at 500 Vdc between Input, Output-1, Output-2, Power Supply, & Grounding Terminals Mutually

Materials of Construction

  • ABS Resin (Black), UL 94 V-0 - Main Unit
  • ABS Resin + Polycarbonate Resin (Black), UL 94 V-0 - Main Unit
  • Modified Polyphenylene Oxide Resin, Including Glass Fiber (Black), UL 94 V-1 - Socket
  • PBT Resin, Including Glass Fiber (Black), UL 94 V-0 - Main Unit

Mounting

  • DIN Rail Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Operating Voltages

  • 12-48 Vdc
  • 85-264 Vac

Output Signal

  • 0-100 mVdc
  • 0-5 mA DC
  • 4-20 mA DC
  • 1-5 Vdc
  • 0-20 mA DC
  • -10 to 10 Vdc
  • -100 to 100 mVdc

Power Supply

  • 100-240 Vac (-15, 10 %) 50/60 Hz - Power Supply Rated & Input Voltage
  • 15-40 Vdc (± 20 %) - Power Supply Rated & Input Voltage

Power Supply Effect

  • Equal to or Less than whichever is greater, ± 0.1 % of Span or Accuracy for the Fluctuation within the Operating Range of Each Power Supply Voltage Specification

Resistance

  • 1 Megaohm - Input Resistance of Voltage Signal (800 kiloohms During Power Off) for 15-40 Vdc & (10 kiloohms During Power Off) for 100-240 Vac
  • 100 ohms (External Receiving Resistor) - Input Resistance of Current Signal
  • 350 to 250,000 ohms - Permissible Load Resistance
  • With 250 ohms Receiving Resistor

Response Time

  • 500 milliseconds, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 1 % of Span or More - Input Adjustment Range
  • ± 5 % of Span or More - Output Adjustment

Supply Voltage

  • 1,000 Vac for 1 Minute between Output-1 & Output-2 Terminals - Withstand Voltage
  • 2,000 Vac for 1 Minute between Input, Output-1 & Output-2, Power Supply & Grounding Terminals Mutually - Withstand Voltage

Temperature Effect

  • ± 0.15 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change
show more