Accuracy
- ± 0.1° C (± 0.18° F) - for RTD Input of the 2-Wire Connection
- ± 0.5° C (± 0.9° F) - Thermocouple for Cold Junction
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) - LCD Visible Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- ATEX Intrinsically Safe
- CE ETSI EN 300 328, ETSI EN 301 489-1, ETSI EN 301 489-17, EN 61010-1, EN 61010-2-030, EN 62311
- CSA Intrinsically Safe
- EMC EN 61326-1 Class A, EN 61326-2-3
- FCC
- FM Intrinsically Safe
- IC
- IECEx Intrinsically Safe
Approvals & Certifications
Battery Life
- 10-Years - at 30 seconds Update Time
- 6 Years - at 10 seconds Update Time
Communication
- Wireless Communication Protocol: ISA100.11a
Diagnostics
- Amplifier Failure
- Battery Alarm
- Configuration Error
- Sensor Failure
- Wireless Communication Alarm & Over-Range Error for Process Variables.
Diameter
- 0.44” (11.2 mm) - Sheath Diameter
Display
- 0 to 100 % Bar Graph
- 5-Digit Numerical Display
- LCD Display
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
Enclosure Finish
- High Anti-Corrosion Coating
- Polyurethane Paint, Mint Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)
Humidity
- 0 to 100 % Relative Humidity
Input
- 2-Wire RTD
- 3-Wire RTD
- 4-Wire RTD
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Tag & Name Plate, Mounting Bracket
Output
- Wireless (ISA100.11a Protocol) 2.4 GHz Signal
Power Requirement
- 2 x Primary Lithium-Thionyl Chloride Batteries
- 7.2 V, 19 Ah Battery
Resistance
- 1 Kiloohm or Lower - Input Signal Source Resistance (For Thermocouple, mV)
- 10 ohms Per Wire or Lower - Input Lead Wire Resistance (For RTD, ohm)
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Temperature Range
- -200° to 1,820° C (-328° to 3,308° F) - Thermocouple
- -200° to 850° C (-328° to 1,562° F) - RTD
Enclosure, Body Material
- Low Copper Cast Aluminum Alloy