YTA510 Wireless Temperature Transmitter

Brand: Yokogawa Electric Corporation

The YTA510 is the high performance temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolt inputs.

The dual input type independently measures and calculates process values for Sensor 1 and Sensor 2.

YTA510 transmit not only process variables but also the setting parameters using wireless signal. In case of the battery powered type, the transmitters run on internal batteries, and the installation cost can be decreased since hard-wiring is not required.

The communication is compliant with ISA100.11a protocol specifications.
Features
  • Long Life Battery Design
  • Security Assured Wireless Network Joining
  • Quick Update Time

Specifications

Accuracy

  • ± 0.1° C (± 0.18° F) - for RTD Input of the 2-Wire Connection
  • ± 0.5° C (± 0.9° F) - Thermocouple for Cold Junction

Ambient Temperature Range

  • -30° to 80° C (-22° to 176° F) - LCD Visible Range
  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • ATEX Intrinsically Safe
  • CE ETSI EN 300 328, ETSI EN 301 489-1, ETSI EN 301 489-17, EN 61010-1, EN 61010-2-030, EN 62311
  • CSA Intrinsically Safe
  • EMC EN 61326-1 Class A, EN 61326-2-3
  • FCC
  • FM Intrinsically Safe
  • IC
  • IECEx Intrinsically Safe

Approvals & Certifications

  • R & TTE Directive

Battery Life

  • 10-Years - at 30 seconds Update Time
  • 6 Years - at 10 seconds Update Time

Burn-Out

  • Downscale
  • Upscale

Communication

  • Wireless Communication Protocol: ISA100.11a

Diagnostics

  • Amplifier Failure
  • Battery Alarm
  • Configuration Error
  • Sensor Failure
  • Wireless Communication Alarm & Over-Range Error for Process Variables.

Diameter

  • 0.44” (11.2 mm) - Sheath Diameter

Display

  • 0 to 100 % Bar Graph
  • 5-Digit Numerical Display
  • LCD Display

Electrical Connectors

  • 1/2” NPT Female
  • G 1/2” Female
  • M20 Female

Enclosure Finish

  • High Anti-Corrosion Coating
  • Polyurethane Paint, Mint Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)

Environmental Protection

  • IP66
  • IP67
  • NEMA 4X

Frequency

  • 2,400 to 2,483.5 MHz

Humidity

  • 0 to 100 % Relative Humidity

Indication

  • Digital

Input

  • 2-Wire RTD
  • 3-Wire RTD
  • 4-Wire RTD

Materials of Construction

  • 304 Stainless Steel - Mounting Bracket
  • 316 Stainless Steel - Tag & Name Plate, Mounting Bracket

Mounting

  • 2” Pipe Mounting Bracket

Mounting Position

  • Horizontal
  • Vertical

Output

  • Wireless (ISA100.11a Protocol) 2.4 GHz Signal

Power

  • Maximum

Power Requirement

  • 2 x Primary Lithium-Thionyl Chloride Batteries
  • 7.2 V, 19 Ah Battery

Resistance

  • 1 Kiloohm or Lower - Input Signal Source Resistance (For Thermocouple, mV)
  • 10 ohms Per Wire or Lower - Input Lead Wire Resistance (For RTD, ohm)

RTD Type

  • Pt100
  • Pt200
  • Pt500

Sensor, Probe Type

  • B Thermocouple
  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • N Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Temperature Range

  • -200° to 1,820° C (-328° to 3,308° F) - Thermocouple
  • -200° to 850° C (-328° to 1,562° F) - RTD

Update Time

  • 1 to 3,600 seconds

Enclosure, Body Material

  • Low Copper Cast Aluminum Alloy
show more