YTA510 Wireless Temperature Transmitter
Brand: Yokogawa Electric CorporationThe YTA510 is the high performance temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolt inputs.
The dual input type independently measures and calculates process values for Sensor 1 and Sensor 2.
YTA510 transmit not only process variables but also the setting parameters using wireless signal. In case of the battery powered type, the transmitters run on internal batteries, and the installation cost can be decreased since hard-wiring is not required.
The communication is compliant with ISA100.11a protocol specifications.
Features- Long Life Battery Design
- Security Assured Wireless Network Joining
- Quick Update Time
Specifications
Accuracy
- ± 0.1° C (± 0.18° F) - for RTD Input of the 2-Wire Connection
- ± 0.5° C (± 0.9° F) - Thermocouple for Cold Junction
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) - LCD Visible Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- ATEX Intrinsically Safe
- CE ETSI EN 300 328, ETSI EN 301 489-1, ETSI EN 301 489-17, EN 61010-1, EN 61010-2-030, EN 62311
- CSA Intrinsically Safe
- EMC EN 61326-1 Class A, EN 61326-2-3
- FCC
- FM Intrinsically Safe
- IC
- IECEx Intrinsically Safe
Approvals & Certifications
- R & TTE Directive
Battery Life
- 10-Years - at 30 seconds Update Time
- 6 Years - at 10 seconds Update Time
Burn-Out
- Downscale
- Upscale
Communication
- Wireless Communication Protocol: ISA100.11a
Diagnostics
- Amplifier Failure
- Battery Alarm
- Configuration Error
- Sensor Failure
- Wireless Communication Alarm & Over-Range Error for Process Variables.
Diameter
- 0.44” (11.2 mm) - Sheath Diameter
Display
- 0 to 100 % Bar Graph
- 5-Digit Numerical Display
- LCD Display
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
Enclosure Finish
- High Anti-Corrosion Coating
- Polyurethane Paint, Mint Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)
Environmental Protection
- IP66
- IP67
- NEMA 4X
Frequency
- 2,400 to 2,483.5 MHz
Humidity
- 0 to 100 % Relative Humidity
Indication
- Digital
Input
- 2-Wire RTD
- 3-Wire RTD
- 4-Wire RTD
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Tag & Name Plate, Mounting Bracket
Mounting
- 2” Pipe Mounting Bracket
Mounting Position
- Horizontal
- Vertical
Output
- Wireless (ISA100.11a Protocol) 2.4 GHz Signal
Power
- Maximum
Power Requirement
- 2 x Primary Lithium-Thionyl Chloride Batteries
- 7.2 V, 19 Ah Battery
Resistance
- 1 Kiloohm or Lower - Input Signal Source Resistance (For Thermocouple, mV)
- 10 ohms Per Wire or Lower - Input Lead Wire Resistance (For RTD, ohm)
RTD Type
- Pt100
- Pt200
- Pt500
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Temperature Range
- -200° to 1,820° C (-328° to 3,308° F) - Thermocouple
- -200° to 850° C (-328° to 1,562° F) - RTD
Update Time
- 1 to 3,600 seconds
Enclosure, Body Material
- Low Copper Cast Aluminum Alloy